Urban Multi Inverter “MX1” Series
WHEN ELECTRIC WIRING WORK IS NOT FINISHED
Remove the electric parts box lid, connect a power supply and remote controller to the terminals.
Next, press the inspection/test operation button “
” on the remote controller. The unit will engage
the test operation mode. Press the operation mode selector button “
” until selecting FAN
OPERATION “
”. Then, press the ON/OFF button “
”. The indoor unit fan and drain pump will
start up. Check that the water has drained from the unit. Press “
” to go back to the first mode.
You can check whether drainage is satisfactory or not by removing the access opening lid and checking
the water level of the drain pan through the access opening.
Be careful when doing so because the fan is turning at the same time.
4-Way Cassette
Type (CS-UM)
1. Rig drain piping
The diameter of the drain pipe should be greater than or equal to the diameter of the connecting pipe
(vinyl tube; pipe size: 25mm; outer dimension: 32mm).
Keep the drain pipe short and sloping downwards at a gradient of at least 1/100 to prevent air pockets
from forming.
If the drain hose cannot be sufficiently set on a slope, execute the drain raising piping.
To keep the drain hose from sagging, space hanging wires every 1 to 1.5 m.
Содержание Urban Multi MX1 Series
Страница 34: ...Installation 1 PACD011001G2 PACD011004G3 34 Urban Multi Inverter MX1 Series Ceiling Type CS TM ...
Страница 54: ...Installation 1 PACD011001G2 PACD011004G3 54 Urban Multi Inverter MX1 Series ...
Страница 102: ...Appendix Check Points in Installing UM Series PACD011001G2 PACD011004G3 102 Urban Multi Inverter MX1 Series ...
Страница 103: ...PACD011001G2 PACD011004G3 Appendix Check Points in Installing UM Series Urban Multi Inverter MX1 Series 103 1 ...
Страница 104: ...Appendix Check Points in Installing UM Series PACD011001G2 PACD011004G3 104 Urban Multi Inverter MX1 Series ...