Installation 1
PACD011001G2 / PACD011004G3
16
Urban Multi Inverter “MX1” Series
Covering of
Refrigerant Pipes
Covering is an extremely important operation as it prevents water, dirt or dust from getting inside
the pipes. Moisture inside the pipes was a constant source of trouble in the past. The utmost care is
required to nip this problem in the bud.
The end of each pieces of pipe must be covered. “Pinching” is the most effective method but “taping” is
an simple alternative which may be used according to the work area and term of work.
1. Pinching method
The end of the copper pipe is squeezed together and the gap brazed.
2. Taping method
The end of the copper pipe is covered with PVC tape (vinyl tape).
<Taping method>
Particular care should be taken during the following operations:
When passing copper pipe through a penetration hole (Dirt easily gets into the pipe).
When copper pipe is located outside (Rainwater gets in )
(Special care is needed when the pipes are standing vertically outside)
Location
Term of Work
Covering Method
Outdoors
1 months or more
Pinching
Less than 1 months
Pinching or taping
Indoors
Irrelevant
Pinching or taping
Содержание Urban Multi MX1 Series
Страница 34: ...Installation 1 PACD011001G2 PACD011004G3 34 Urban Multi Inverter MX1 Series Ceiling Type CS TM ...
Страница 54: ...Installation 1 PACD011001G2 PACD011004G3 54 Urban Multi Inverter MX1 Series ...
Страница 102: ...Appendix Check Points in Installing UM Series PACD011001G2 PACD011004G3 102 Urban Multi Inverter MX1 Series ...
Страница 103: ...PACD011001G2 PACD011004G3 Appendix Check Points in Installing UM Series Urban Multi Inverter MX1 Series 103 1 ...
Страница 104: ...Appendix Check Points in Installing UM Series PACD011001G2 PACD011004G3 104 Urban Multi Inverter MX1 Series ...