PACD011001G2 / PACD011004G3
Installation 1
Urban Multi Inverter “MX1” Series
35
Wall Type (CS-KM)
Floor Standing Type, Concealed Floor Standing Type (CS-PM, CS-RM)
3.2.6
Electrical Work
Control Wiring
1. Compatible types of wire
Wiring Specifications
Notes:
1. Sheathed wire may be used for transmission winings, but they do not comply with EMI (Electromagnetic
lnterference) (EN55014). When using sheathed wire. EMI must conform to Japanese standards
stipulated in the Electric Appliance Regulatory Act. (If using a sheathed wire, the grounding shown in
the figure on the left is unnecessary.)
2. For CS-KM indoor unit, use sheathed wire.
2. Problems arising from the use of unsuitable cable
a) When cable less than 0.75 mm² is used
Where the control wiring is particularly long the transmission signals may, for example, become
unstable and the terminal relay cease to function. (Reduced voltage) The control system may become
unduly subject to noise interference.
Wiring Type
Shield Wire (2 wire) (See NOTE 1, 2)
Size
0.75~1.25 mm²