Bad Examples and Good Examples in Installation
PACD011001G2 / PACD011004G3
72
Urban Multi Inverter “MX1” Series
7.2
Example 2:
Mismatch between cables connecting indoor and outdoor units
and corresponding piping
. (all model)
Situation
The remote controller is not showing any malfunction and the system is operating but there is no flow of
warm air from the indoor unit (in heating mode).
Source of Problem
and Remedial
Action
The connecting cables and the corresponding piping were not correctly matched.
Recabling was carried out and the fault disappeared.
Main Points
Special care must be taken when the pipework and cabling are carried out by different people.
Run each indoor unit in turn to check that the system is correctly matched.