PACD011001G2 / PACD011004G3
Installation 1
Urban Multi Inverter “MX1” Series
23
Grouped Drain
Piping
1. It is standard work practice to make connections to the main pipe from above. The pipe down from the
combination should be as large as possible.
2. The pipework should be kept as short as possible and the number of indoor units per group kept to a
minimum.
Use of an Auxiliary
Drain Hose
(Flexible)
If a drain pan made of polystyrene foam is used then an auxiliary drain hose (flexible) is also essential. A
flexible drain hose permits the drain socket and drain pipe to be connected without difficulty and prevents
any undue strain being placed on the drain pan.
Important points
1. The drain pipe should be at least equal in size to that of the indoor unit.
2. The drain pipe is thermally insulated to prevent the formation of condensation inside the pipe.
3. The drain up mechanism should be fitted before the indoor unit is installed and when the electricity has
been connected some water should be added to the drain pan and the drain pump checked to see that
it is functioning correctly.
4. All connections should be secure. (Special care is needed with PVC pipe)
The use of a colored adhesive with PVC pipes will help you to remember to connect them up.)
Содержание Urban Multi MX1 Series
Страница 34: ...Installation 1 PACD011001G2 PACD011004G3 34 Urban Multi Inverter MX1 Series Ceiling Type CS TM ...
Страница 54: ...Installation 1 PACD011001G2 PACD011004G3 54 Urban Multi Inverter MX1 Series ...
Страница 102: ...Appendix Check Points in Installing UM Series PACD011001G2 PACD011004G3 102 Urban Multi Inverter MX1 Series ...
Страница 103: ...PACD011001G2 PACD011004G3 Appendix Check Points in Installing UM Series Urban Multi Inverter MX1 Series 103 1 ...
Страница 104: ...Appendix Check Points in Installing UM Series PACD011001G2 PACD011004G3 104 Urban Multi Inverter MX1 Series ...