Installation 1
PACD011001G2 / PACD011004G3
42
Urban Multi Inverter “MX1” Series
Service Space
It is extremely important that enough space is left when installing the equipment to allow routine servicing
and maintenance to be carried out without undue hindrance. It is particularly important to bear in mind the
work which will be required if the compressor needs to be replaced. (The layout of the pipework can
sometimes cause considerable difficulties if the compressor needs to be changed.)
Prevention of
Short
Circuits
The unit must be installed in a well ventilated area, otherwise short circuiting will occur. Special care should
be taken in situations such as that illustrated in the diagram below since additional fittings such as air
discharge ducts may also be required. (Attention should be paid to the duct’s resistance)
Conditions for installation under the eaves
When L
≥
1m then N must be
≥
M.
When L < 1m then K must be
≥
M.
Where K is the required dimension for a single
unit installation.
Conditions for installation where there is a
horizontal obstruction above the unit
When L
≥
3m then no special action is required.
When L < 3m then a air discharge duct with
resistance within 3mmH
2
O is required.
Where K measures a little more than the
required K dimension for a single unit
installation.
Содержание Urban Multi MX1 Series
Страница 34: ...Installation 1 PACD011001G2 PACD011004G3 34 Urban Multi Inverter MX1 Series Ceiling Type CS TM ...
Страница 54: ...Installation 1 PACD011001G2 PACD011004G3 54 Urban Multi Inverter MX1 Series ...
Страница 102: ...Appendix Check Points in Installing UM Series PACD011001G2 PACD011004G3 102 Urban Multi Inverter MX1 Series ...
Страница 103: ...PACD011001G2 PACD011004G3 Appendix Check Points in Installing UM Series Urban Multi Inverter MX1 Series 103 1 ...
Страница 104: ...Appendix Check Points in Installing UM Series PACD011001G2 PACD011004G3 104 Urban Multi Inverter MX1 Series ...