Piping Diameter for
Grouped Drain
Pipes
Select piping diameter from the below table in accordance with the amount of condensation drained by
all units with a common drain pipe.
Consider 2 l/hr of drainage for every 1 HP. For example, drainage from 3 units running at 2 HP and 2
units running at 3 HP is calculated as follows.
2 (l/hr) × 2 (HP) × 3 (units) + 2 (l/hr) × 3 (HP) × 2 (units) = 24 l/hr
1. Relationship between horizontal pipe diameter and allowable drainage (for extended ventilation system)
Notes:
Calculations have been made with water area inside the pipe as 10%.
Allowable flow rate figures below the decimal have been discarded.
Use VP30 or larger pipe after the convergence point.
2. Relationship between riser diameter and allowable drainage (for extended ventilation system)
Notes:
Allowed flow rate figures below the decimal have been discarded.
Use VP30 or larger pipe in risers.
Use the same drain pipe for the humidifier as the indoor unit.
3.2.5
Drain Piping for Each Model
2-Way Cassette
Type (CS-LM)
1. Rig drain piping
The diameter of the drain pipe should be greater than or equal to the diameter of the connecting pipe
(vinyl tube; pipe size: 25mm; outer dimension: 32mm).
Keep the drain pipe short and sloping downwards at a gradient of at least 1/100 to prevent air pockets
from forming.
If the drain hose cannot be sufficiently set on a slope, execute the drain raising piping.
To keep the drain hose from sagging, space hanging wires every 1 to 1.5 m.
Use the attached drain hose and clamp metal.
Insert the drain hose into the drain socket, up to the white tape. Tighten the clamp until the screw head
is less than 4 mm from the hose.
Wrap the attached sealing pad over the clamp and drain hose to insulate.
JIS nominal
Vinyl chloride pipe
diameter (mm)
Allowable flow rate (l/hr)
Remarks
Piping gradient 1:50
Piping gradient 1:100
VP20
20
39
27
(Reference value) Cannot
be used in grouped piping.
VP25
25
70
50
VP30
31
125
88
Can be used in grouped
piping.
VP40
40
247
175
VP50
51
473
334
JIS nominal
Vinyl chloride pipe
diameter (mm)
Allowable flow rate
(l/hr)
Remarks
VP20
20
220
(Reference value) Cannot
be used in grouped piping.
VP25
25
410
VP30
31
730
Can be used in grouped
piping.
VP40
40
1440
VP50
51
2760
VP65
67
5710
VP75
77
8280
Содержание Urban Multi MX1 Series
Страница 34: ...Installation 1 PACD011001G2 PACD011004G3 34 Urban Multi Inverter MX1 Series Ceiling Type CS TM ...
Страница 54: ...Installation 1 PACD011001G2 PACD011004G3 54 Urban Multi Inverter MX1 Series ...
Страница 102: ...Appendix Check Points in Installing UM Series PACD011001G2 PACD011004G3 102 Urban Multi Inverter MX1 Series ...
Страница 103: ...PACD011001G2 PACD011004G3 Appendix Check Points in Installing UM Series Urban Multi Inverter MX1 Series 103 1 ...
Страница 104: ...Appendix Check Points in Installing UM Series PACD011001G2 PACD011004G3 104 Urban Multi Inverter MX1 Series ...