8.1
Operating Noise of Indoor Units
8.1.1
Difference Between Catalogue Data and Actual Noise
Operating noise differs depending on the place of measurement (room) because of the various degrees
with which the room reverberates the sound. To determine the amount of reverberation under uniform
conditions, the unit has been measured in a dead room with results having been compiled in the below
table. The actual sound produced in unit operation can be determined from Table 1.
Sound pressure rise due to room reverberation (Higher than catalogue data)
Table 1
A
B
C
Room interior detection
Floor
Mortar
Linoleum tile
Carpet
Walls
Mortar
Plaster
Fiberglass
+
Saroncross finish
Ceiling
Mortar
mineral wool tile
Fiberglass
+
Saroncross finish
Average absorbed sound (room with
approx. 50 m² floor area)
0.05
0.12
0.25
Typical office
Estimated value to be added to
catalogue value (dB)
11 ~ 12
8 ~ 8.5
5 ~ 6
Содержание Urban Multi MX1 Series
Страница 34: ...Installation 1 PACD011001G2 PACD011004G3 34 Urban Multi Inverter MX1 Series Ceiling Type CS TM ...
Страница 54: ...Installation 1 PACD011001G2 PACD011004G3 54 Urban Multi Inverter MX1 Series ...
Страница 102: ...Appendix Check Points in Installing UM Series PACD011001G2 PACD011004G3 102 Urban Multi Inverter MX1 Series ...
Страница 103: ...PACD011001G2 PACD011004G3 Appendix Check Points in Installing UM Series Urban Multi Inverter MX1 Series 103 1 ...
Страница 104: ...Appendix Check Points in Installing UM Series PACD011001G2 PACD011004G3 104 Urban Multi Inverter MX1 Series ...