Installation 2
PACD011001G2 / PACD011004G3
58
Urban Multi Inverter “MX1” Series
Settings
Example for Inverter MX1 Series
Field settings mode with the remote controller
With the Inverter MX1 Series, all field settings are made from the remote controller of the indoor unit.
A description of each setting is provided on the below table.
For details on how to make settings, refer to the operation manual and / or installation manual of the
unit.
Setting Contents and Code No.
UM
system
indoor
unit
settings
Mode
No.
Note 2
First
Code
No.
Setting Contents
Second Code No.(Note 3)
01
02
03
04
10(20)
0
Filter contamination heavy/light
(Setting for display time to
clean air filter)
(Sets display time to clean air
filter to half when there is
heavy filter contamination.)
Super
long life
filter
Light
Approx.
10,000
hrs.
Heavy
Approx.
5,000
hrs.
—
—
Long life
filter
Approx.
2,500
hrs.
Approx.
1,250
hrs.
Standard
filter
Approx.
200 hrs.
Approx.
100 hrs.
1
Long life filter type
(CS-LM only, 01 indicates long life)
Long life filter
Super long life filter
—
Soot filter
2
Thermostat sensor in remote controller
Use
No use
—
3
Display time to clean air filter calculation
(Set when filter sign is not to be displayed.)
Display
No display
—
12(22)
0
Optional accessories output selection (field
selection of output for adaptor for wiring)
Indoor unit turned
ON by thermostat
Operation output
Malfunction output
1
ON/OFF input from outside (Set when ON/
OFF is to be controlled from outside.)
Forced OFF
ON/OFF control
External protection
device
—
2
Thermostat differential changeover
(Set when remote sensor is to be used.)
CS-LM, CS-UM, CS-DM, CS-TM only
1°C
0.5°C
—
—
3
OFF by thermostat fan speed
LL
Set fan speed
—
—
4
Automatic mode differential (automatic
temperature differential setting for UM
system heat recovery series cool/heat)
01:0
02:1
03:2
4:03
05:4
6:05
7:06
08:7
5
Power failure automatic reset
Not equipped
Equipped
—
—
13(23)
0
High air outlet velocity
(Set when installed in place with ceiling
higher than 2.7 m.) CS-UM only
N
H
—
—
1
Selection of air flow direction
(Set when a blocking pad kit has been
installed.) CS-UM only
F (4 directions)
T (3 directions)
W (2 directions)
—
2
Horizontal air discharge
Equipped
Not equipped
—
3
Air flow direction adjustment (Set at
installation of decoration panel.) CS-DM
only
Equipped
Not equipped
—
4
Field set air flow position setting
Draft prevention
Standard
Ceiling Soiling
prevention
—
5
Field set fan speed selection
(fan speed control by air discharge outlet
for phase control)
Standard
Optional
accessory 1
Optional accessory
2
—
15(25)
1
Thermostat OFF excess humidity
Not equipped
Equipped
—
—
3
Drain pump humidifier interlock selection
Not equipped
Equipped
—
—
4
Sets whether filter sign is to be output by
time or by input.
Time addition
Input
—
—
5
Field set selection for individual ventilation
setting by remote controller
Not equipped
Equipped
—
—
6
Field set selection for individual ventilation
setting by remote controller
Not equipped
Equipped
—
—
Содержание Urban Multi MX1 Series
Страница 34: ...Installation 1 PACD011001G2 PACD011004G3 34 Urban Multi Inverter MX1 Series Ceiling Type CS TM ...
Страница 54: ...Installation 1 PACD011001G2 PACD011004G3 54 Urban Multi Inverter MX1 Series ...
Страница 102: ...Appendix Check Points in Installing UM Series PACD011001G2 PACD011004G3 102 Urban Multi Inverter MX1 Series ...
Страница 103: ...PACD011001G2 PACD011004G3 Appendix Check Points in Installing UM Series Urban Multi Inverter MX1 Series 103 1 ...
Страница 104: ...Appendix Check Points in Installing UM Series PACD011001G2 PACD011004G3 104 Urban Multi Inverter MX1 Series ...