INSTALLATION AND CONNECTIONS
© Panasonic Industrial Devices SUNX Co., Ltd. 2019
3-22
●
HG-SC112 / NPN output type
*S1
*S1
*S1
(Pink) External input 1
(Violet) External input 2
(Pink / Violet) External input 3
Main circuit
Connect to +V (brown) of
HG-SC101
Connect to 0V (blue) of
HG-SC101
(Black) Output 1
(White) Output 2
(Black / Gray) Output 3
Load
Load
Load
*S1
Non-voltage contact or NPN open collector transistor
or
0 to +1.2V DC: Valid
+8V to +V DC or open: Invalid
Note: Use shielded wire for the analog output.
<Reference>
●
All outlets are equipped with short-circuit protection. If any one of outputs 1 to 3 short-circuits,
all outputs temporarily turn OFF. The outputs automatically recover when the short-circuit state
is cleared.
●
The
HG-SC112
cable does not have +V or 0V. Power is supplied from the connector of the mas-
ter unit.