7-5 Error Messages
If an error occurs during configuration of settings or measurement, one of the error numbers be
-
low will appear.
Error number
Cause
Solution
E100
Both NPN output types and PNP
output types are connected.
Connect only units of the same output type.
E110
Number of connectable units ex-
ceeded.
Connect no more than 15 slave units per master unit.
(When communication unit consolidated: up to 14 slave units)
E120
Cannot communicate between con-
trollers.
Switch OFF the power, make sure the controllers are
connected correctly, and then switch ON the power
again.
E130
E140
The calculation function is valid but
no slave units are connected.
Change calculation mode to OFF.
E150
The calculation function is valid but
an insufficient number of slave units
are connected.
Change calculation mode to OFF, or change the calcu-
lation application selection setting.
E160
The saved number of connected
units does not match the actual
number of connected units.
Set the number of connected units check function to
OFF.
E200
• Sensor head not connected.
• Broken wire in sensor head con-
nection cable.
• Sensor head failure.
• Check if the sensor head is correctly connected.
• Check if there is a broken wire in the sensor head
connection cable. If there is a broken wire in the sen-
sor head connection cable, replace the cable.
• Replace the sensor head.
E210
The thrust on the sensor head
stroke is above the specified range.
Check the sensor head mounting and measurement ob-
ject installation position, and adjust so that the stroke is
within the specified range.
E500
Unable to preset by external input.
Check if the power has just been switched on or reset
has just been input, or if a display value is outside the
display upper/lower limit or an alarm has occurred.
E600
• Failed to write to or read from EE-
PROM.
• The EEPROM write count is over
the service life of 1 million.
• Switch the power OFF then ON, and execute initializa-
tion of the controller from setting mode.
• If the controller does not recover after the above, it is
possible that the EEPROM write count is over 1 mil-
lion. Replace the controller.
E610
E620
E700
The detection output load has short-
circuited and excessive current is
flowing.
Switch OFF the power and check the load.
E900
An error has occurred in the internal
controller.
Switch the power OFF then ON, and execute initializa-
tion of the controller from setting mode.
E910
E911
E912
E920
<Important>
If an error occurs again after you cleared it,
●
Check if an excessive force is applied to the controller or the sensor head.
●
If the product still does not operate normally after you check the above, consult our technical
support center.
Содержание HG-S Series
Страница 2: ... Panasonic Industrial Devices SUNX Co Ltd 2019 2 MEMO ...
Страница 7: ...1 1 Chapter 1 INTRODUCTION 1 1 Safety Cautions 1 2 1 2 Safety Information 1 2 ...
Страница 44: ... Panasonic Industrial Devices SUNX Co Ltd 2019 3 24 MEMO ...
Страница 72: ... Panasonic Industrial Devices SUNX Co Ltd 2019 4 28 MEMO ...
Страница 75: ... Panasonic Industrial Devices SUNX Co Ltd 2019 5 3 MEMO ...
Страница 174: ... Panasonic Industrial Devices SUNX Co Ltd 2019 5 102 MEMO ...
Страница 175: ...6 1 Chapter 6 SPECIFICATIONS 6 1 Specifications 6 2 6 2 Dimensions 6 7 ...
Страница 188: ... Panasonic Industrial Devices SUNX Co Ltd 2019 6 14 MEMO ...
Страница 198: ... MEMO ...