INSTALLATION AND CONNECTIONS
© Panasonic Industrial Devices SUNX Co., Ltd. 2019
3-21
●
HG-SC111-P / PNP output type
*S1
*S1
*S1
(Pink) External input 1
(Violet) External input 2
(Pink / Violet) External input 3
Connect to 0V (blue) of
HG-SC101-P
Main circuit
Connect to +V (brown) of
HG-SC101-P
(Black) Output 1
(Gray) Analog current output (4 to 20mA)
(250Ω max.)
(Shielded) Analog ground (Note)
(White) Output 2
(Black / Gray) Output 3
Load
Load
Load
Load
AGND
*S1
Non-voltage contact or PNP open collector transistor
or
+4V to +V DC: Valid
0 to +0.6V DC or open: Invalid
Note: Use shielded wire for the analog output.
<Reference>
●
All outlets are equipped with short-circuit protection. If any one of outputs 1 to 3 short-circuits,
all outputs temporarily turn OFF. The outputs automatically recover when the short-circuit state
is cleared.
●
The
HG-SC111-P
cable does not have +V or 0V. Power is supplied from the connector of the
master unit.
Содержание HG-S Series
Страница 2: ... Panasonic Industrial Devices SUNX Co Ltd 2019 2 MEMO ...
Страница 7: ...1 1 Chapter 1 INTRODUCTION 1 1 Safety Cautions 1 2 1 2 Safety Information 1 2 ...
Страница 44: ... Panasonic Industrial Devices SUNX Co Ltd 2019 3 24 MEMO ...
Страница 72: ... Panasonic Industrial Devices SUNX Co Ltd 2019 4 28 MEMO ...
Страница 75: ... Panasonic Industrial Devices SUNX Co Ltd 2019 5 3 MEMO ...
Страница 174: ... Panasonic Industrial Devices SUNX Co Ltd 2019 5 102 MEMO ...
Страница 175: ...6 1 Chapter 6 SPECIFICATIONS 6 1 Specifications 6 2 6 2 Dimensions 6 7 ...
Страница 188: ... Panasonic Industrial Devices SUNX Co Ltd 2019 6 14 MEMO ...
Страница 198: ... MEMO ...