Remove the Motherboard
Caution -
Take care when using the handles to remove the motherboard. These handles are not
in weight-balanced locations. Avoid flexing the motherboard. Also, if DIMMs are installed,
take care not to flex them.
9.
Tilt the motherboard the other direction, and slowly lift the motherboard up and
out of the server.
10.
Set the motherboard aside on an antistatic surface.
11.
Consider your next step.
■
If replacing a faulty motherboard, install a new motherboard.
See
“Install the Motherboard” on page 231
.
■
If you removed the motherboard as part of another component's service
procedure, return to that procedure.
See
“Component Service Task Reference” on page 47
.
Related Information
■
“Install the Motherboard” on page 231
230
Netra SPARC S7-2 Server Service Manual • February 2017
Содержание Netra SPARC S7-2
Страница 1: ...Netra SPARC S7 2 Server Service Manual Part No E73207 03 February 2017 ...
Страница 2: ......
Страница 12: ...12 Netra SPARC S7 2 Server Service Manual February 2017 ...
Страница 24: ...24 Netra SPARC S7 2 Server Service Manual February 2017 ...
Страница 42: ...Server Fault Remind Button Operation 42 Netra SPARC S7 2 Server Service Manual February 2017 ...
Страница 84: ...84 Netra SPARC S7 2 Server Service Manual February 2017 ...
Страница 108: ...108 Netra SPARC S7 2 Server Service Manual February 2017 ...
Страница 140: ...140 Netra SPARC S7 2 Server Service Manual February 2017 ...
Страница 150: ...150 Netra SPARC S7 2 Server Service Manual February 2017 ...
Страница 158: ...158 Netra SPARC S7 2 Server Service Manual February 2017 ...
Страница 192: ...192 Netra SPARC S7 2 Server Service Manual February 2017 ...
Страница 216: ...216 Netra SPARC S7 2 Server Service Manual February 2017 ...
Страница 258: ...258 Netra SPARC S7 2 Server Service Manual February 2017 ...