Secure the Drive Cage
5.
If you installed the PSU duct as part of another component's service procedure,
return to that procedure.
“Component Service Task Reference” on page 47
for assistance.
Related Information
■
“Remove the PSU Duct” on page 74
■
“Install the Air Duct” on page 236
Secure the Drive Cage
Perform this task once you have pivoted the drive cage to the service position.
1.
If you previously removed the PSU and air ducts, complete these prerequisites
in this order.
See:
■
“Install the Air Duct” on page 236
■
“Install the PSU Duct” on page 240
2.
Lower the drive cage to the horizontal position.
Returning a Server to Operation
241
Содержание Netra SPARC S7-2
Страница 1: ...Netra SPARC S7 2 Server Service Manual Part No E73207 03 February 2017 ...
Страница 2: ......
Страница 12: ...12 Netra SPARC S7 2 Server Service Manual February 2017 ...
Страница 24: ...24 Netra SPARC S7 2 Server Service Manual February 2017 ...
Страница 42: ...Server Fault Remind Button Operation 42 Netra SPARC S7 2 Server Service Manual February 2017 ...
Страница 84: ...84 Netra SPARC S7 2 Server Service Manual February 2017 ...
Страница 108: ...108 Netra SPARC S7 2 Server Service Manual February 2017 ...
Страница 140: ...140 Netra SPARC S7 2 Server Service Manual February 2017 ...
Страница 150: ...150 Netra SPARC S7 2 Server Service Manual February 2017 ...
Страница 158: ...158 Netra SPARC S7 2 Server Service Manual February 2017 ...
Страница 192: ...192 Netra SPARC S7 2 Server Service Manual February 2017 ...
Страница 216: ...216 Netra SPARC S7 2 Server Service Manual February 2017 ...
Страница 258: ...258 Netra SPARC S7 2 Server Service Manual February 2017 ...