Install the PSU Duct
Related Information
■
“Install the PSU Duct” on page 240
■
“Remove the Air Duct” on page 75
■
“Secure the Drive Cage” on page 241
Install the PSU Duct
Perform this task when you have previously removed the PSU duct.
1.
Install the air duct.
See
“Install the Air Duct” on page 236
.
2.
Lower the PSU duct down over the PDB and the bus bars.
3.
Route the USB cable over the PSU duct to the USB board.
4.
Route the USB cable through the cutout in the air duct, and push the cable into
the channel in the PSU duct.
240
Netra SPARC S7-2 Server Service Manual • February 2017