Wiring Control Circuit Terminals
2-
27
Control Circuit Wiring Precautions
Observe the following precautions when wiring control circuits.
•
Separate control circuit wiring from main circuit wiring (terminals R/L1, S/L2, T/L3, B1, B2, U/T1, V/T2,
W/T3, , 1, 2,
and 3)
and
other
high-power
lines.
•
Separate wiring for control circuit terminals MA, MB, MC, M1, and M2 (contact outputs) from wiring to
other control circuit terminals.
•
Use twisted-pair or shielded twisted-pair cables for control circuits to prevent operating faults. Process
cable ends as shown in
Fig 2.20
.
•
Connect the shield wire to terminal E (G).
•
Insulate the shield with tape to prevent contact with other signal lines and equipment.
Fig 2.20 Processing the Ends of Twisted-pair Cables
Shield sheath
Armor
Connect to shield sheath ter-
minal at Inverter (terminal E
(G))
Insulate with tape
Do not connect here.