6
-76
Monitor Constants
This section explains the analog monitor and pulse monitor constants.
Using the Analog Monitor Constants
This section explains the analog monitor constants.
Related Constants
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
Display
V/f
V/f
with
PG
Open
Loop
Vector
1
Flux
Vec-
tor
Open
Loop
Vector
2
H4-01
Monitor
selection (ter-
minal FM)
Sets the number of the monitor item
to be output (U1-
) from termi-
nal FM.
4, 10 to 14, 25, 28, 34, 39, 40 cannot
be set. 29 to 31 and 41 are not used.
1 to 45
2
No
A
A
A
A
A
Terminal FM
Sel
H4-02
Gain (termi-
nal FM)
Sets the multi-function analog out-
put 1 voltage level gain.
Sets whether the monitor item out-
put will be output in multiples of
10 V.
The maximum output from the ter-
minal is 10 V. A meter calibration
function is available.
0.00 to
2.50
(0 to
1000.0)
1.00
(100%)
Yes
Q
Q
Q
Q
Q
Terminal FM
Gain
H4-03
Bias (termi-
nal FM)
Sets the multi-function analog out-
put 1 voltage level bias.
Sets output characteristic up/down
parallel movement as a percentage
of 10 V.
The maximum output from the ter-
minal is 10 V. A meter calibration
function is available.
-10.0 to
+10.0
(-100.0
to 100.0)
0.0%
(0.0%)
Yes
A
A
A
A
A
Terminal FM
Bias
H4-04
Monitor
selection (ter-
minal AM)
Sets the number of the monitor item
to be output (U1-
) from termi-
nal AM.
4, 10 to 14, 25, 28, 34, 39, 40 cannot
be set. 29 to 31 and 41 are not used.
1 to 45
3
No
A
A
A
A
A
Terminal AM
Sel
H4-05
Gain (termi-
nal AM)
Set the voltage level gain for multi-
function analog output 2.
Set the number of multiples of 10 V
to be output as the 100% output for
the monitor items. The maximum
output from the terminal is 10 V. A
meter calibration function is avail-
able.
0.00 to
2.50
(0 to
1000.0)
0.50
(200%)
Yes
Q
Q
Q
Q
Q
Terminal AM
Gain
H4-06
Bias (termi-
nal AM)
Sets the multi-function analog out-
put 2 voltage level bias.
Sets output characteristic up/down
parallel movement as a percentage
of 10 V.
The maximum output from the ter-
minal is 10 V. A meter calibration
function is available.
-10.0 to
+10.0
(0 to
1000.0)
0.0%
(0.0%)
Yes
A
A
A
A
A
Terminal AM
Bias