Wiring Control Circuit Terminals
Wire Sizes and Closed-loop Connectors
For remote operation using analog signals, keep the control line length between the Digital Operator or opera-
tion signals and the Inverter to 50 m or less, and separate the lines from high-power lines (main circuits or
relay sequence circuits) to reduce induction from peripheral devices.
When setting frequencies from an external frequency setter (and not from a Digital Operator), used shielded
twisted-pair wires and ground the shield to terminal E (G), as shown in the following diagram.
Fig 2.14
Terminal numbers and wire sizes are shown in
Table 2.9
.
* 1. Use shielded twisted-pair cables to input an external frequency reference.
* 2. Refer to
Table 2.3 Close-loop Connector Sizes
for suitable closed-loop crimp terminal sizes for the wires.
* 3. We recommend using straight solderless terminal on signal lines to simplify wiring and improve reliability.
Table 2.9 Terminal Numbers and Wire Sizes (Same for all Models)
Terminals
Termi-
nal
Screws
Tightening
Torque
(N•m)
Possible Wire
Sizes
mm
2
(AWG)
Recom-
mended
Wire Size
mm
2
(AWG)
Wire Type
FM, AC, AM, M3, M4,
SC, A1, A2, A3, +V, -V,
S1, S2, S3, S4, S5, S6,
S7, S8, MA, MB, MC,
M1, M2, P3, C3, P4, C4,
MP, RP, R+, R-, S9, S10,
S11, S12, S+, S-, IG, SN,
SP
Phoenix
type
0.5 to 0.6
Single wire
*3
:
0.14 to 2.5
Stranded wire:
0.14 to 1.5
(26 to 14)
0.75
(18)
• Shielded, twisted-pair wire
*1
• Shielded, polyethylene-cov-
ered, vinyl sheath cable
(KPEV-S by Hitachi Electri-
cal Wire or equivalent)
E (G)
M3.5
0.8 to 1.0
0.5 to 2
*2
(20 to 14)
1.25
(12)
Shield ter-
Speed setting power supply, +15 V 20 mA
Master speed reference, -10 to 10 V
Master speed reference, 4 to 20 mA
Pulse input, 32 kHz
Auxiliary reference
Analog common
2 k
Ω
2 k
Ω
2 k
Ω
2 k
Ω