User Constant Tables
5-
11
* The setting range is 0 or 1 for flux vector control and open-loop vector control 2.
b1-05
Operation
selection
for setting
E1-09 or
less
Used to set the method of
operation when the fre-
quency reference input is less
than the minimum output fre-
quency (E1-09).
0: Run at frequency reference
(E1-09 not effective).
1: STOP (Frequencies below
E1-09 in the coast to stop
state.)
2: Run at min. frequency.
(E1-09)
3: Run at zero speed (Fre-
quencies below E1-09 are
zero)
0 to 3
0
No
No
No
No
A
No
184H
6-9
Zero-Speed
Oper
b1-06
Read
sequence
input twice
Used to set the responsiveness
of the control inputs (forward/
reverse and multi-function
inputs.)
0: Two scans every 2 ms (Use
for fast responses.)
1: Two scans every 5 ms (Use
for possible malfunction
due to noise.)
0 or 1
1
No
A
A
A
A
A
185H
-
Cntl Input
Scans
b1-07
Operation
selection
after
switching to
remote
mode
Used to set the operation mode
by switching to the Remote
mode using the Local/Remote
Key.
0: Run signals that are input
during mode switching are
disregarded. (Input Run
signals after switching the
mode.)
1: Run signals become
effective immediately after
switching to the Remote
mode.
0 or 1
0
No
A
A
A
A
A
186H
-
LOC/REM
RUN Sel
b1-08
Run com-
mand selec-
tion in
program-
ming modes
Used to set an operation inter-
lock in programming modes.
0: Cannot operate.
1: Can operate (Disabled
when Digital Operator is
set to select run command
(when b1-02 = 0).
0 or 1
0
No
A
A
A
A
A
187H
-
RUN CMD
at PRG
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
Содержание VARISPEED G7 -
Страница 3: ......
Страница 11: ...viii...
Страница 33: ...1 16...
Страница 105: ...4 20...
Страница 349: ...6 154...
Страница 375: ...7 26...
Страница 413: ...10 24...
Страница 417: ......