User Constant Tables
5-
77
U1-15
Terminal
A1 input
voltage
Monitors the input voltage of
the voltage frequency refer-
ence. An input of 10 V corre-
sponds to 100%.
10 V: 100% (10 V)
(0 to ± 10 V possible)
0.1
%
A
A
A
A
A
4EH
Term A1
Level
U1-16
Terminal
A2 input
voltage
Monitors the input voltage of
the multi-function analog
input.
An input of 10 V corresponds
to 100%.
10 V: 100% (10 V)
(0 to ±10 V possible)
0.1
%
A
A
A
A
A
4FH
Term A2
Level
U1-17
Terminal
A3 input
voltage
Monitors the input voltage of
the multi-function analog
input.
An input of 10 V corresponds
to 100%.
10 V: 100% (10 V)
(0 to ±10 V possible)
0.1
%
A
A
A
A
A
050H
Term 16
Level
U1-18
Motor sec-
ondary cur-
rent (Iq)
Monitors the calculated value
of the motor secondary cur-
rent.
The motor rated secondary
current corresponds to 100%.
10 V: Motor rated
secondary current)
(0 to ±10 V output)
0.1
%
A
A
A
A
A
51H
Mot SEC
Current
U1-19
Motor
exciting
current (Id)
Monitors the calculated value
of the motor excitation cur-
rent.
The motor rated secondary
current corresponds to 100%.
10 V: Motor rated
secondary current)
(0 to ±10 V output)
0.1
%
No
No
A
A
A
52H
Mot EXC
Current
U1-20
Output fre-
quency
after soft-
start
Monitors the output frequency
after a soft start.
The frequency given does not
include compensations, such
as slip compensation.
The unit is set in o1-03.
10 V: Max. frequency
(0 to ± 10 V possible)
0.0
1Hz
A
A
A
A
A
53H
SFS Output
U1-21
ASR input
Monitors the input to the speed
control loop.
The maximum frequency cor-
responds to 100%.
10 V: Max. frequency
(0 to ± 10 V possible)
0.0
1%
No
A
No
A
A
54H
ASR Input
U1-22
ASR output Monitors the output from the
speed control loop.
The motor rated secondary
current corresponds to 100%.
10 V: Motor rated
secondary current)
(0 to ± 10 V possible)
0.0
1%
No
A
No
A
A
55H
ASR Out-
put
U1-24
PID feed-
back value
Monitors the feedback value
when PID control is used.
The input for the max. fre-
quency corresponds to 100%.
10 V: Max. frequency
(0 to ± 10 V possible)
0.0
1%
A
A
A
A
A
57H
PID Feed-
back
U1-25
DI-16H2
input status
Monitors the reference value
from a DI-16H2 Digital Refer-
ence Card.
The value will be displayed in
binary or BCD depending on
user constant F3-01.
(Cannot be output.)
-
A
A
A
A
A
58H
DI-16 Ref-
erence
Con-
stant
Number
Name
Description
Output Signal Level
During Multi-Function
Analog Output
Min.
Unit
Control Methods
MEMO
BUS
Regis-
ter
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
Содержание VARISPEED G7 -
Страница 3: ......
Страница 11: ...viii...
Страница 33: ...1 16...
Страница 105: ...4 20...
Страница 349: ...6 154...
Страница 375: ...7 26...
Страница 413: ...10 24...
Страница 417: ......