User Constant Tables
5-
53
Multi-function Analog Outputs: H4
User constants for multi-function analog outputs are shown in the following table.
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
H4-01
Monitor
selection
(terminal
FM)
Sets the number of the monitor
item to be output (U1-
)
from terminal FM.
4, 10 to 14, 25, 28, 34, 39, 40
cannot be set. 29 to 31 and 41
are not used.
1 to 45
2
No
A
A
A
A
A
41DH 6-76
Terminal
FM Sel
H4-02
Gain (ter-
minal FM)
Sets the multi-function analog
output 1 voltage level gain.
Sets whether the monitor item
output will be output in multi-
ples of 10 V.
The maximum output from the
terminal is 10 V. A meter cali-
bration function is available.
0.00 to
2.50
(0 to
1000.0)
1.00
(100%)
Yes
Q
Q
Q
Q
Q
41EH
4-6
6-76
Terminal
FM Gain
H4-03
Bias (termi-
nal FM)
Sets the multi-function analog
output 1 voltage level bias.
Sets output characteristic up/
down parallel movement as a
percentage of 10 V.
The maximum output from the
terminal is 10 V. A meter cali-
bration function is available.
-10.0 to
+10.0
(-100.0
to
100.0)
0.0%
(0.0%)
Yes
A
A
A
A
A
41FH
4-6
Terminal
FM Bias
H4-04
Monitor
selection
(terminal
AM)
Sets the number of the monitor
item to be output (U1-
)
from terminal AM.
4, 10 to 14, 25, 28, 34, 39, 40
cannot be set. 29 to 31 and 41
are not used.
1 to 45
3
No
A
A
A
A
A
420H
4-6
6-76
Terminal
AM Sel
H4-05
Gain (ter-
minal AM)
Set the voltage level gain for
multi-function analog output 2.
Set the number of multiples of
10 V to be output as the 100%
output for the monitor items.
The maximum output from the
terminal is 10 V. A meter cali-
bration function is available.
0.00 to
2.50
(0 to
1000.0)
0.50
(200%)
Yes
Q
Q
Q
Q
Q
421H
4-6
6-76
Terminal
AM Gain
H4-06
Bias (termi-
nal AM)
Sets the multi-function analog
output 2 voltage level bias.
Sets output characteristic up/
down parallel movement as a
percentage of 10 V.
The maximum output from the
terminal is 10 V. A meter cali-
bration function is available.
-10.0 to
+10.0
(0 to
1000.0)
0.0%
(0.0%)
Yes
A
A
A
A
A
422H
-
Terminal
AM Bias
H4-07
Analog out-
put 1 signal
level selec-
tion
Sets the signal output level for
multi-function output 1 (termi-
nal FM)
0: 0 to +10 V output
1: 0 to ±10 V output
0 or 1
0
No
A
A
A
A
A
423H
-
AO Level
Select1