Adjusting Frequency References
6-
27
Operation Avoiding Resonance (Jump Frequency Function)
The jump frequency function operates the motor while avoiding resonance caused by characteristic frequen-
cies in the machinery.
This function is effective in creating a frequency reference dead band.
During constant-speed operation, operation within the jump frequency range is prohibited. Smooth operation
still used during acceleration and deceleration, i.e., jumps are not performed.
Related Constants
The relationship between the output frequency and the jump frequency reference is as follows:
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
Display
V/f
V/f
with
PG
Open
Loop
Vector
1
Flux
Vec-
tor
Open
Loop
Vector
2
d3-01
Jump fre-
quency 1
Set the center values of the jump
frequencies in Hz.
This function is disabled by set-
ting the jump frequency to 0 Hz.
Always ensure that the following
applies:
d3-01
≥
d3-02
≥
d3-03
Operation in the jump frequency
range is prohibited but during
acceleration and deceleration,
speed changes smoothly without
jump.
0.0 to
400.0
0.0 Hz
No
A
A
A
A
A
Jump Freq 1
d3-02
Jump fre-
quency 2
0.0 Hz
No
A
A
A
A
A
Jump Freq 2
d3-03
Jump fre-
quency 3
0.0 Hz
No
A
A
A
A
A
Jump Freq 3
d3-04
Jump fre-
quency width
Sets the jump frequency band-
width in Hz.
The jump frequency will be the
jump frequency ± d3-04.
0.0 to
20.0
1.0 Hz
No
A
A
A
A
A
Jump Band-
width
Terminal A1 input voltage
Frequency reference
H3-02
10%
Bias
0 V
10 V