Monitor Constants
6-
79
Using Pulse Train Monitor Contents
This section explains pulse monitor constants.
Related Constants
Selecting Pulse Monitor Items
Output digital operator monitor items (U1-
[status monitor]) from pulse monitor terminal MP-SC. Refer
to
Chapter 5 User Constants
, and set the
part of U1-
(Status monitor). The possible monitor selec-
tions are limited as follows: U1-01, 02, 05, 20, 24, 36.
Adjusting the Pulse Monitor Items
Adjust the pulse frequency output from pulse monitor terminal MP-SC. Set the pulse frequency output when
100% frequency is output to H6-07.
Set H6-06 to 2, and H6-07 to 0, to output the frequency synchronous with the Inverter's U-phase output.
Application Precautions
When using a pulse monitor constant, connect a peripheral device according to the following load conditions.
If the load conditions are different, there is a risk of characteristic insufficiency or damage to the machinery.
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
Display
V/f
V/f
with
PG
Open
Loop
Vector
1
Flux
Vec-
tor
Open
Loop
Vector
2
H6-06
Pulse train
monitor
selection
Select the pulse train monitor output
items (value of the
part of U1-
).
There are two types of monitor
items: Speed-related items and PID-
related items.
1, 2, 5,
20, 24,
36
2
Yes
A
A
A
A
A
Pulse Output
Sel
H6-07
Pulse train
monitor scal-
ing
Set the number of pulses output
when speed is 100% in hertz.
Set H6-06 to 2, and H6-07 to 0, to
make the pulse train monitor output
synchronously to the output fre-
quency.
0 to
32000
1440 Hz
Yes
A
A
A
A
A
PO Scaling
Using a Sourcing Output
Output Voltage
(Isolated)
VRL (V)
Load Impedance (k
Ω
)
+5 V min.
1.5 k
Ω
min.
+8 V min.
3.5 k
Ω
min.
+10 V min.
10 k
Ω
min.
Load impedance
MP
AC
VRL
Содержание VARISPEED G7 -
Страница 3: ......
Страница 11: ...viii...
Страница 33: ...1 16...
Страница 105: ...4 20...
Страница 349: ...6 154...
Страница 375: ...7 26...
Страница 413: ...10 24...
Страница 417: ......