User Constant Tables
5-
27
Note The unit is set in o1-03 (frequency units of reference setting and monitor). The default for o1-03 is 0 (increments of 0.01 Hz).
* The setting range is 0 to 66.0 for open-loop vector control 2.
Reference Limits: d2
User constants for frequency reference limits are shown in the following table.
d1-12
Frequency
reference 12
The frequency reference
when multi-step speed refer-
ences 1, 2, and 4 are ON for
multi-function inputs.
0 to
400.00
*
0.00 Hz
Yes
A
A
A
A
A
28DH
-
Reference 12
d1-13
Frequency
reference 13
The frequency reference
when multi-step speed refer-
ences 3 and 4 are ON for
multi-function inputs.
0.00 Hz
Yes
A
A
A
A
A
28EH
-
Reference 13
d1-14
Frequency
reference 14
The frequency reference
when multi-step speed refer-
ences 1, 3, and 4 are ON for
multi-function inputs.
0.00 Hz
Yes
A
A
A
A
A
28FH
-
Reference 14
d1-15
Frequency
reference 15
The frequency reference
when multi-step speed refer-
ences 2, 3, and 4 are ON for
multi-function inputs.
0.00 Hz
Yes
A
A
A
A
A
290H
-
Reference 15
d1-16
Frequency
reference 16
The frequency reference
when multi-step speed refer-
ences 1, 2, 3, and 4 are ON
for multi-function inputs.
0.00 Hz
Yes
A
A
A
A
A
291H
-
Reference 16
d1-17
Jog frequency
reference
The frequency reference
when the jog frequency refer-
ence selection, FJOG com-
mand, or RJOG command is
ON.
6.00 Hz
Yes
Q
Q
Q
Q
Q
292H
4-6
6-74
Jog
Reference
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
d2-01
Frequency
reference
upper limit
Set the output frequency
upper limit as a percent, tak-
ing the max. output frequency
to be 100%.
0.0 to
110.0
100.0%
No
A
A
A
A
A
289H
6-30
6-69
Ref Upper
Limit
d2-02
Frequency
reference
lower limit
Sets the output frequency
lower limit as a percentage of
the maximum output fre-
quency.
0.0 to
110.0
0.0%
No
A
A
A
A
A
28AH
6-30
6-69
Ref Lower
Limit
d2-03
Master speed
reference
lower limit
Set the master speed refer-
ence lower limit as a percent,
taking the max. output fre-
quency to be 100%.
0.0 to
110.0
0.0%
No
A
A
A
A
A
293H
6-30
6-69
Ref1 Lower
Limit
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2