User Constant Tables
5-
49
Multi-function Contact Output Functions
Set-
ting
Value
Function
Control Methods
Page
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
0
During run (ON: run command is ON or voltage is being output)
Yes
Yes
Yes
Yes
Yes
-
1
Zero-speed
Yes
Yes
Yes
Yes
Yes
-
2
Frequency agree 1 (L4-02 used.)
Yes
Yes
Yes
Yes
Yes
-
3
Desired frequency agree 1 (ON: Output frequency = ±L4-01, L4-02 used and dur-
ing frequency agree)
Yes
Yes
Yes
Yes
Yes
-
4
Frequency (FOUT) detection 1 (ON: +L4-01
≥
output frequency
≥
-L4-01, L4-02
used)
Yes
Yes
Yes
Yes
Yes
-
5
Frequency (FOUT) detection 2 (ON: Output frequency
≥
+L4-01 or output fre-
quency
≤
-L4-01, L4-02 used)
Yes
Yes
Yes
Yes
Yes
-
6
Inverter operation ready
READY: After initialization, no faults
Yes
Yes
Yes
Yes
Yes
-
7
During DC bus undervoltage (UV) detection
Yes
Yes
Yes
Yes
Yes
-
8
During baseblock (ON: during baseblock)
Yes
Yes
Yes
Yes
Yes
-
9
Frequency reference selection (ON: Frequency reference from Operator)
Yes
Yes
Yes
Yes
Yes
-
A
Run command selection status (ON: Run command from Operator)
Yes
Yes
Yes
Yes
Yes
-
B
Overtorque/undertorque detection 1 NO (NO contact: Overtorque/undertorque
detection at ON)
Yes
Yes
Yes
Yes
Yes
6-46
C
Loss of frequency reference (Effective when 1 is set for L4-05)
Yes
Yes
Yes
Yes
Yes
6-62
D
Braking resistor fault (ON: Resistor overheat or braking transistor fault)
Yes
Yes
Yes
Yes
Yes
6-64
E
Fault (ON: Digital Operator communications error or fault other than CPF00 and
CPF01 has occurred.)
Yes
Yes
Yes
Yes
Yes
-
F
Not used. (Set when the terminals are not used.)
-
-
-
-
-
-
10
Minor fault (ON: Alarm displayed)
Yes
Yes
Yes
Yes
Yes
-
11
Fault reset command active
Yes
Yes
Yes
Yes
Yes
-
12
Timer function output
Yes
Yes
Yes
Yes
Yes
6-93
13
Frequency agree 2 (L4-04 used)
Yes
Yes
Yes
Yes
Yes
-
14
Desired frequency agree 2 (ON: Output frequency = L4-03, L4-04 used, and dur-
ing frequency agree)
Yes
Yes
Yes
Yes
Yes
-
15
Frequency detection 3 (ON: Output frequency
≤
-L4-03, L4-04 used)
Yes
Yes
Yes
Yes
Yes
-
16
Frequency detection 4 (ON: Output frequency
≥
-L4-03, L4-04 used)
Yes
Yes
Yes
Yes
Yes
-
17
Overtorque/undertorque detection 1 NC (NC Contact: Torque detection at OFF)
Yes
Yes
Yes
Yes
Yes
6-46
18
Overtorque/undertorque detection 2 NO (NO Contact: Torque detection at ON)
Yes
Yes
Yes
Yes
Yes
6-46
19
Overtorque/undertorque detection 2 NC (NC Contact: Torque detection at OFF)
Yes
Yes
Yes
Yes
Yes
6-46
1A
During reverse run (ON: During reverse run)
Yes
Yes
Yes
Yes
Yes
-
1B
During baseblock 2 (OFF: During baseblock)
Yes
Yes
Yes
Yes
Yes
-
1C
Motor selection (Motor 2 selected)
Yes
Yes
Yes
Yes
Yes
-
1D
During regenerative operation (ON: During regenerative operation)
No
No
No
Yes
Yes
-
1E
Restart enabled (ON: Restart enabled)
Yes
Yes
Yes
Yes
Yes
6-63
1F
Motor overload (OL1, including OH3) pre-alarm (ON: 90% or more of the detec-
tion level)
Yes
Yes
Yes
Yes
Yes
6-49
20
Inverter overheat (OH) pre-alarm (ON: Temperature exceeds L8-02 setting)
Yes
Yes
Yes
Yes
Yes
-
30
During torque limit (current limit) (ON: During torque limit)
No
No
Yes
Yes
Yes
-
Содержание VARISPEED G7 -
Страница 3: ......
Страница 11: ...viii...
Страница 33: ...1 16...
Страница 105: ...4 20...
Страница 349: ...6 154...
Страница 375: ...7 26...
Страница 413: ...10 24...
Страница 417: ......