User Constant Tables
5-
39
* The factory setting will change when the control method is changed. (Flux vector control factory settings are given.)
F1-05
PG rotation
0: Phase A leads with
forward run command.
(Phase B leads with
reverse run command.)
1: Phase B leads with
forward run command.
(Phase A leads with
reverse run command.)
0 or 1
0
No
No
A
No
A
No
384H
6-
142
PG Rotation
Sel
F1-06
PG division
rate (PG
pulse moni-
tor)
Sets the division ratio for the
PG speed control card pulse
output.
Division ratio = (1+ n) /m
(n=0 or 1 m=1 to 32)
This constant is only effective
when a PG-B2 is used.
The possible division ratio
settings are: 1/32
≤
F1-06
≤
1.
1 to
132
1
No
No
A
No
A
No
385H
6-
143
PG Output
Ratio
F1-07
Integral value
during accel/
decel enable/
disable
Sets integral control during
acceleration/deceleration to
either enabled or disabled.
0: Disabled (The integral
function isn't used while
accelerating or
decelerating; it is used at
constant speeds.)
1: Enabled (The integral
function is used at all
times.)
0 or 1
0
No
No
A
No
No
No
386H
6-
143
PG Ramp PI/I
Sel
F1-08
Overspeed
detection
level
Sets the overspeed detection
method.
Frequencies above that set for
F1-08 (set as a percentage of
the maximum output fre-
quency) that continue to
exceed this frequency for the
time set in F1-09 are detected
as overspeed faults.
0 to
120
115%
No
No
A
No
A
A
387H
6-
143
PG Overspd
Level
F1-09
Overspeed
detection
delay time
0.0 to
2.0
0.0 s
*
No
No
A
No
A
A
388H
6-
143
PG Overspd
Time
F1-10
Excessive
speed devia-
tion detec-
tion level
Sets the speed deviation
detection method.
Any speed deviation above
the F1-10 set level (set as a
percentage of the maximum
output frequency) that contin-
ues for the time set in F1-11 is
detected as a speed deviation.
Speed deviation is the differ-
ence between actual motor
speed and the reference com-
mand speed.
0 to 50
10%
No
No
A
No
A
A
389H
6-
143
PG Deviate
Level
F1-11
Excessive
speed devia-
tion detec-
tion delay
time
0.0 to
10.0
0.5 s
No
No
A
No
A
A
38AH
6-
143
PG Deviate
Time
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor