Trial Operation Procedures
4-
7
Settings for the Control Methods
Autotuning methods depend on the control method set for the Inverter. Make the settings required by the con-
trol method.
Overview of Settings
Make the required settings in quick programming mode and autotuning mode according to the following flow-
chart.
Note If the motor cable changes to 50 m or longer for the actual installation, perform stationary autotuning for the line-to-line resistance only on-site.
* 1. Use rotational autotuning to increase autotuning accuracy whenever it is okay for the motor to be operated. Always perform rotational autotuning when
using open-loop vector control 2.
* 2. If there is a reduction gear between the motor and PG, set the reduction ratio in F1-12 and F1-13.
* 3. The default setting of the Inverter is for open-loop vector control 1 (A1-02 = 2).
* 4. If the maximum output frequency and base frequency are different, set the maximum output frequency (E1-04) after autotuning.
Fig 4.3 Settings According to the Control Method
START
YES
V/f
V/f control?
(A1-02 = 0 or 1)
PG?
Motor cable over
50 m or heavy load possibly
causing motor to stall
or overload?
NO
(Default: A1-02 = 0)
YES
(A1-02 = 1)
NO
Vector (A1-02 = 2, 3, or 4)*3
Set E1-03.
V/f default: 200 V/60 Hz(400 V/60 Hz)
Set E1-03, E2-04, and F1-01.
V/f default: 200 V/60 Hz(400 V/60 Hz)
NO
YES
YES
NO
END
*2
Control mode selection
OK to operate
motor during autotuning?*1
Rotational autotuning*4
Stationary autotuning*4
Stationary autotuning for
line-to-line resistance only
Содержание VARISPEED G7 -
Страница 3: ......
Страница 11: ...viii...
Страница 33: ...1 16...
Страница 105: ...4 20...
Страница 349: ...6 154...
Страница 375: ...7 26...
Страница 413: ...10 24...
Страница 417: ......