* 1. These are values for a 200 V Class Inverter. Values for a 400 V Class Inverter are double.
* 2. The factory setting will change when the control method is changed. (Open-loop vector control factory settings are given.)
* 3. The contents of constants E1-11 and E1-12 are ignored when set to 0.00.
* 4. E1-13 is set to the same value as E1-05 by autotuning.
* 5. The setting range is 0 to 66.0 for open-loop vector control 2.
Setting Inverter Input Voltage
Set the Inverter input voltage correctly in E1-01 to match the power supply voltage. This set value will be the
standard value for the protection function and similar functions.
Setting V/f Pattern
Set the V/f pattern in E1-03 when using V/f control (with or without a PG). There are two methods of setting
the V/f pattern: Select one of the 15 pattern types (set value: 0 to E) that have been set beforehand, or set a
user-defined V/f pattern (set value: F).
The factory setting for E1-03 is F. The contents of E1-03 when factory-set to F are the same as when E1-03 is
set to 1.
To select one of the existing patterns, refer to the following table.
E1-11
Mid. output
frequency 2
Set only to fine-adjust V/f for the output
range. Normally, this setting is not
required.
0.0 to
400.0
*5
0.0 Hz
*3
No
A
A
A
A
A
Mid
Frequency B
E1-12
Mid. output
frequency
voltage 2
0.0 to
255.0
*1
0.0 V
*3
No
A
A
A
A
A
Mid Voltage
B
E1-13
Base voltage
0.0 to
255.0
*1
0.0 V
*4
No
A
A
Q
Q
Q
Base Voltage
Characteristic
Application
Set
Value
Specifications
Constant Torque
Characteristic
This pattern is used in general applications.
Used when the load torque is fixed, regard-
less of rotation speed, for linear transport
systems.
0
50 Hz specifications
1 (F)
60 Hz specifications
2
60 Hz specifications, voltage saturation at
50 Hz
3
72 Hz specifications, voltage saturation at
60 Hz
Variable torque
characteristic
This pattern is used for loads with torque
proportional to two or three times the rota-
tion speed, such as fans and pumps.
4
50 Hz specifications,
×
3 decrement
5
50 Hz specifications,
×
2 decrement
6
60 Hz specifications,
×
3 decrement
7
60 Hz specifications,
×
2 decrement
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
Display
V/f
V/f
with
PG
Open
Loop
Vector
1
Flux
Vec-
tor
Open
Loop
Vector
2