4-5
Section
Connection Examples
68
Process Flow
•
Set the unit numbers for each of the V530-R150s.
(In this example, the unit numbers are set to 00, 01, and 02.)
•
After the V530-R150 reads a code, it holds the data without
outputting it. Polling commands are sent out in order from the
host and the data is downloaded.
Note If a reading trigger is turned ON before the data is downloaded,
the V530-R150 will operate as shown below and the previous
reading data will be overwritten.
START
Host
Reading
trigger input
V530-R150
Unit number 00
V530-R150
Unit number 01
V530-R150
Unit number 02
Reads code
Polling command
to output data
Data output from
unit number 00
@RD 00(CR)
Data response
00ABCDEFG...(CR)
Data output from
unit number 01
@RD 01(CR)
01ABCDEFG...(CR)
Data output from
unit number 02
@RD 02(CR)
02ABCDEFG...(CR)
Completion of
data output
Reads code
Reads code
Data response
Data response