SIEPCYEUOQ2V01A Q2V Technical Manual
551
Register
No. (Hex.)
Description
15EF
Slave Address for Reg. During Modbus process & ErrCode
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
bit 7
00H: Modbus Communication Complete
02H: Register number not registered
21H: Upper/Lower Limit Fault
22H: Write Mode Error
23H: Write performed during
Uv
24H: Write performed while writing parameter settings
FFH: During Modbus Communication
Note:
If you change the access command before the Modbus access flag turns on, the drive
will not do the command from before.
bit 8
bit 9
bit A
bit B
Slave address
0: Modbus command ignored
1: Drive 1
2: Drive 2
3: Drive 3
4: Drive 4
5: Broadcast Messages (run command and frequency
reference)
bit C -
F
Reserved
15F0
Register number
15F1
Data (write register)
■
F6-01: Comm.Error Selection
No.
(Hex.)
Name
Description
Default
(Range)
F6-01
(03A2)
Comm.Error Selection
Sets the method to stop the motor or let the motor continue operating when the drive detects
bUS
[Option Communication Error]
.
1
(0 - 5)
0 : Ramp->Stop
The drive ramps the motor to stop in the deceleration time. The output terminal set for
Fault [H2-01 to H2-03 =
3]
activates.
1 : Coast->Stop
The output turns off and the motor coasts to stop. The output terminal set for
Fault [H2-01 to H2-03 = 3]
activates.
2 : Fast Stop (C1-09)
The drive stops the motor in the deceleration time set in
C1-09 [Fast Stop Time]
. The output terminal set for
Fault
[H2-01 to H2-03 = 3]
activates.
3 : Alarm Only
The keypad shows
bUS
and the drive continues operation at the current frequency reference.
Note:
Separately prepare safety protection equipment and systems, for example fast stop switches.
The output terminal set to
Alarm [H2-01 to H2-03 = 4]
activates.
4 : AL-Run at d1-04
The keypad shows
bUS
and the drive continues operation at the speed set in
d1-04 [Reference 4]
.
Note:
Separately prepare safety protection equipment and systems, for example fast stop switches.
5 : AL-Ramp Stop
The drive stops the motor during the deceleration time set in
C1-02 [Decel Time 1]
.
After you remove the
bUS
alarm, the motor will accelerate to the previous frequency reference.
■
F6-02: Comm Ext Flt Detect (EF0)
No.
(Hex.)
Name
Description
Default
(Range)
F6-02
(03A3)
Comm Ext Flt Detect (EF0)
Sets the conditions at which
EF0 [Option Card External Fault]
is detected.
0
(0, 1)
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание Q2V Series
Страница 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Страница 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 143: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 143 EU Declaration of Conformity...
Страница 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Страница 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...
Страница 733: ...SIEPCYEUOQ2V01A Q2V Technical Manual 733...