Timers prevent sensors and switches from making chattering noise.
There are two types of timers:
•
Timers that set a delay for timer inputs and timer outputs.
These timers delay activating and deactivating of the MFDIs and MFDOs.
To enable this function, set
H1-xx = 60 [MFDI Function Select = Timer Fn Input], and set H2-01 to H2-03 =
39 [MFDO Function Select = Timer Output]
.
•
Timers that set a delay to activate and deactivate MFDO terminals.
These timers delay activating and deactivating MFDO terminals.
To enable this function, set delay times in parameters
b4-03 to b4-08
.
■
Timer Function Operation
•
Timers that Set a Delay for Timer Inputs and Timer Outputs
Triggers timer output if the timer input is active for longer than the time set in
b4-01 [Timer Function ON-Delay
Time]
. Triggers timer output late for the time set in
b4-02 [Timer Function OFF-Delay Time]
.
shows an example of how the timer function works.
Figure 12.26 Example of Timer Function Operation
•
Setting On/Off-delay Time for MFDO
uses H2-01 terminals to show an example of how the timer function works. Use
b4-03 [Terminal
M1-M2 ON-Delay Time]
and
b4-04 [Terminal M1-M2 OFF-Delay Time]
to set this function.
Figure 12.27 Example of How the Timer Function Works with H2-01 Terminals
Note:
When the terminal is triggered, it continues for a minimum of 100 ms. The on/off-delay time of MFDO terminal does not have an effect.
■
b4-01: Timer ON Time Delay
No.
(Hex.)
Name
Description
Default
(Range)
b4-01
(01A3)
Timer ON Time Delay
Sets the ON-delay time for the timer input.
0.0 s
(0.0 - 3000.0 s)
■
b4-02: Timer OFF Time Delay
No.
(Hex.)
Name
Description
Default
(Range)
b4-02
(01A4)
Timer OFF Time Delay
Sets the OFF-delay time for the timer input.
0.0 s
(0.0 - 3000.0 s)
■
b4-03: NO,NC,CM ON-Time Delay
No.
(Hex.)
Name
Description
Default
(Range)
b4-03
(0B30)
Expert
NO,NC,CM ON-Time
Delay
Sets the delay time until the contact is turned ON after the function set with
H2-01
turns ON.
0 ms
(0 - 65000 ms)
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание Q2V Series
Страница 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Страница 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 143: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 143 EU Declaration of Conformity...
Страница 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Страница 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...
Страница 733: ...SIEPCYEUOQ2V01A Q2V Technical Manual 733...