SIEPCYEUOQ2V01A Q2V Technical Manual
No.
(Hex.)
Name
Description
MFAO Signal Level
U4-18
(07DA)
FRef Source Selected
Shows the selected frequency reference source.
The keypad shows the frequency reference source as
“
XY-nn
”
as specified by these rules:
X:
Ext Ref 1/2 [H1-xx = 9]
selection status
•
1:
b1-01 [Freq. Ref. Sel. 1]
•
2:
b1-15 [Freq. Ref. Sel. 2]
Y-nn: Frequency reference source
•
0-01: Keypad (
d1-01 [Reference 1]
)
•
1-00: Analog input (unassigned)
•
1-01: MFAI terminal AI1
•
1-02: MFAI terminal AI2
•
2-02 to 2-17: Multi-step speed reference (
d1-02 to d1-17 [Reference 2 to Reference 16, Jog
Reference]
)
•
3-01: Modbus communications
•
4-01: Communication option card
•
5-01: Pulse train input
•
7-01: Q2pack
•
9-01: Up/Down command
No signal output available
U4-19
(07DB)
Mbus FreqReference Value
Shows the frequency reference sent to the drive from the Modbus communications as a decimal.
Unit: 0.01%
10 V = Maximum
frequency (-10 V to +10 V)
U4-20
(07DC)
Option FreqReference
Value
Shows the frequency reference sent to the drive from the communication option as a decimal.
10 V = Maximum
frequency (-10 V to +10 V)
U4-21
(07DD)
Run Source Selected
Shows the selected Run command source.
The keypad shows the Run command source as
“
XY-nn
”
as specified by these rules:
X:
Ext Ref 1/2 [H1-xx = 9]
selection status
•
1:
b1-02 [Run Comm. Sel 1]
•
2:
b1-16 [Run Comm. Sel 2]
Y: Run command source
•
0: Keypad
•
1: Control circuit terminal
•
3: Modbus communications
•
4: Communication option card
•
7: Q2pack
nn: Run command limit status data
•
00: No limit status.
•
01: The Run command was left ON when the drive stopped in the Programming Mode.
•
02: The Run command was left ON when switching from LOCAL Mode to REMOTE Mode.
•
03: The Run command is in standby after the drive was energized until the soft charge bypass
contactor turns ON.
Note:
The drive will detect
Uv1 [DC Bus Undervoltage]
or
Uv [Undervoltage]
if the soft charge
bypass contactor does not turn ON after 10 s.
•
04: Restart after run stop is prohibited.
•
05: Fast stop has been executed using the MFDI terminal. Or, the motor has ramped to stop by
pressing the STOP key on the keypad.
•
06:
b1-17 = 1 [RUN@PowerUp Selection = Disregard RUN]
is set.
•
07: During baseblock while coast to stop with timer.
•
08: Frequency reference is below
E1-09 [Min Output Frequency]
during baseblock.
•
09: Waiting for the Enter command from PLC.
No signal output The
keypad shows the Run
command source as "XY-
nn" as specified by these
rules: available
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание Q2V Series
Страница 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Страница 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 143: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 143 EU Declaration of Conformity...
Страница 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Страница 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...
Страница 733: ...SIEPCYEUOQ2V01A Q2V Technical Manual 733...