When the MFDI terminal set to
PID Disable [H1-xx = 6A]
activates, the drive disables fault detection.
4 : AL+DO@PID Enable
The drive detects
FbL
and
FbH
. The MFDO terminal set for
PID Feedback Low
or
PID Feedback High
activates.
The output terminal set for
Alarm [H2-01 to H2-03 = 4]
activates and the drive continues operation.
When the MFDI terminal set to
PID Disable [H1-xx = 6A]
activates, the drive disables fault detection.
5 : FLT+DO@PID Enable
The drive detects
FbL
and
FbH
. MFDO terminal NO-CM turns ON, NC-CM turns OFF, and the drive coasts to
stop.
When the MFDI terminal set to
PID Disable [H1-xx = 6A]
activates, the drive disables fault detection.
■
b5-13: Fdback Loss Lvl
No.
(Hex.)
Name
Description
Default
(Range)
b5-13
(01B1)
Fdback Loss Lvl
Sets the level that triggers
PID Feedback Loss [FbL]
detection as a percentage of the Maximum
Output Frequency.
0%
(0 - 100%)
The drive detects
PID Feedback Loss [FbL]
when the feedback signal decreases to less than the level set in
b5-13
for longer than the time set in
b5-14 [Fdback Loss Time]
.
■
b5-14: Fdback Loss Time
No.
(Hex.)
Name
Description
Default
(Range)
b5-14
(01B2)
Fdback Loss Time
Sets the length of time that PID Feedback must be less than
b5-13 [Fdback Loss Lvl]
to detect
PID Feedback Loss [FbL]
.
1.0 s
(0.0 - 25.5 s)
■
b5-15: Sleep Start Level
No.
(Hex.)
Name
Description
Default
(Range)
b5-15
(01B3)
Sleep Start Level
Sets the output level that triggers the PID Sleep function.
Determined by A1-02
(0.0 - 590.0)
The drive goes into Sleep mode when the PID output or frequency reference is less than
b5-15
for longer than the
time set to
b5-16 [Sleep Delay Time]
. The drive continues operation when the PID output or frequency reference
is more than
b5-15
for longer than the time set to
b5-16
.
■
b5-16: Sleep Delay Time
No.
(Hex.)
Name
Description
Default
(Range)
b5-16
(01B4)
Sleep Delay Time
Sets a delay time to start or stop the PID Sleep function.
0.0 s
(0.0 - 25.5 s)
■
b5-17: PID Accel/Decel Time
No.
(Hex.)
Name
Description
Default
(Range)
b5-17
(01B5)
RUN
PID Accel/Decel Time
Raises or lowers the PID setpoint using the acceleration and deceleration times set to the drive.
This is a soft-starter for the PID setpoint.
0.0 s
(0.0 - 6000.0 s)
The drive usually uses the acceleration and deceleration times set in
C1: ACCEL / DECEL
, but when PID control
is enabled, the drive applies
C1-xx
after PID output. If you frequently change the PID setpoint, the drive
responsiveness decreases. When resonance with PID control causes hunting, overshoot, or undershoot, set
b5-17
for longer acceleration and deceleration times.
Decrease
C1-xx
until hunting stops, then use
b5-17
to check the acceleration and deceleration. To enable and
disable the setting in
b5-17
through an MFDI terminal, set
PID SS Cancel [H1-xx = 75]
.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание Q2V Series
Страница 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Страница 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 143: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 143 EU Declaration of Conformity...
Страница 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Страница 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...
Страница 733: ...SIEPCYEUOQ2V01A Q2V Technical Manual 733...