580
SIEPCYEUOQ2V01A Q2V Technical Manual
Note:
Refer to
“
C5: ASR - SPEED REGULATION on page 499
for more information.
■
46: ASR I Reset
Setting Value
Function
Description
46
ASR I Reset
Sets the command to reset the integral value and use PI control or P control for the speed control loop.
ON : P control
OFF : PI control
■
60: Timer Fn Input
Setting Value
Function
Description
60
Timer Fn Input
Sets the command to start the timer function. Use this setting with
Timer Output [H2-xx = 39]
.
Note:
Refer to
“
for more information.
■
61: Motor 2 Select
Setting Value
Function
Description
61
Motor 2 Select
Sets the command for the drive to operate motor 1 or motor 2. Stop the motors before switching.
You can use an external input to switch operation between two induction motors. The drive will save the control
methods, V/f patterns, and motor parameters for the two motors.
ON : Operate motor 2
OFF : Operate motor 1
When you select motor 2, the drive will switch to motor 2 parameters.
Table 12.40 Parameters that Switch between Motor 1 and Motor 2
Parameter
Motor 2 Selection
OFF (Motor 1)
ON (Motor 2)
C1: ACCEL / DECEL
C1-01 to C1-04
C1-05 to C1-08
C3: SLIP COMPENSATION
C3-01 to C3-04
C3-21 to C3-24
C4: TORQUE COMPENSATION
C4-01
C4-07
C5: ASR - SPEED REGULATION
C5-01 to C5-08, C5-12
-
E1: V/F PARAMETER MOTOR 1, E2:
MOTOR 1 PARAMETERS, E3: V/F
PARAMETER MOTOR 2, E4: MOTOR 2
PARAMETERS
E1-xx, E2-xx
E3-xx, E4-xx
Note:
•
When you use 2 motors, the drive applies the protective function set in
L1-01 [Motor Cool Type for OL1 Calc]
to motor 1 and motor 2.
•
You cannot switch between motors 1 and 2 during run. If you try to switch motors when they are running, it will cause a
rUn
error.
•
You must wait 200 ms minimum to input a Run command.
■
62: Up Command
Setting Value
Function
Description
62
Up Command
Sets the command to use a push button switch to increase the drive frequency reference. You must also set
Setting 63 [Down
Command]
.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание Q2V Series
Страница 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Страница 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 143: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 143 EU Declaration of Conformity...
Страница 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Страница 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...
Страница 733: ...SIEPCYEUOQ2V01A Q2V Technical Manual 733...