SIEPCYEUOQ2V01A Q2V Technical Manual
481
■
b5-89: Sleep Method Selection
No.
(Hex.)
Name
Description
Default
(Range)
b5-89
(0B89)
RUN
Sleep Method Selection
Sets sleep and wake up operation when using PID.
0
(0, 1)
0 : Standard
1 : EZ Sleep/Wake-up
■
b5-90: EZsleep Unit
No.
(Hex.)
Name
Description
Default
(Range)
b5-90
(0B90)
EZsleep Unit
Sets the measurement units for
b5-91 [EZsleep Min Spd]
and
b5-92 [EZsleep Level]
.
0
(0, 1)
0 : rpm
1 : 0.1Hz units
■
b5-91: EZsleep Min Spd
No.
(Hex.)
Name
Description
Default
(Range)
b5-91
(0B91)
RUN
EZsleep Min Spd
Sets the minimum speed for the EZ Sleep/Wakeup function. This parameter uses the largest value
from
b5-91
,
b5-34 [PID Out Low Limit Level]
, and
d2-02 [FRef Lower Limit]
.
0.0 Hz or 0 min
-1
(r/min)
(0.0 to 590.0 Hz or 0 to
35400 min
-1
(r/min))
Note:
The value of
b5-90 [b5-91: EZsleep Unit]
sets the units. When
b5-90
changes, this parameter does not automatically update. Set this
parameter again after you change
b5-90
is changed.
■
b5-92: EZsleep Level
No.
(Hex.)
Name
Description
Default
(Range)
b5-92
(0B92)
RUN
EZsleep Level
Sets the value that the output frequency or motor speed must be less than for longer than
b5-93
[EZsleep Time]
to enter Sleep Mode.
0.0 Hz or 0 min
-1
(r/min)
(0.0 to 590.0 Hz or 0 to
35400 min
-1
(r/min))
Note:
When
b5-90 [EZsleep Unit]
changes, this parameter does not automatically update. Set this parameter again after you change
b5-90
.
■
b5-93: EZsleep Time
No.
(Hex.)
Name
Description
Default
(Range)
b5-93
(0B93)
RUN
EZsleep Time
Sets the length of time that the output frequency or motor speed must be less than
b5-92 [EZsleep
Level]
to enter Sleep Mode.
5.0 s
(0.0 - 1000.0 s)
■
b5-94: EZsleep Wake Level
No.
(Hex.)
Name
Description
Default
(Range)
b5-94
(0B94)
RUN
EZsleep Wake Level
Sets the level at which the drive resumes operation when exiting Sleep Mode.
0.00%
(0.00 - 600.00%)
Note:
The values of
b5-20 [PID Unit Selection]
,
b5-38 [PID SP User Scale for Display]
, and
b5-39 [PID SP User digits for Display]
set the
units. When
b5-20
,
b5-38
, and
b5-39
change, this parameter does not automatically update. Set this parameter again after you change
b5-20
,
b5-38
, and
b5-39
are changed.
•
When
b5-95 = 1 [EZsleep Wake Mode = Absolute]
:
When
b5-09 = 0 [PID Output Level Selection = Normal output]
, and the PID Feedback
[H3-xx = F]
is less than
the value of
b5-94
for a time longer than the value of
b5-96 [EZsleep Wake Time]
, the drive will exit sleep and
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание Q2V Series
Страница 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Страница 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 143: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 143 EU Declaration of Conformity...
Страница 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Страница 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...
Страница 733: ...SIEPCYEUOQ2V01A Q2V Technical Manual 733...