SIEPCYEUOQ2V01A Q2V Technical Manual
59
Model
Terminal
Recommended Gauge
mm
2
Applicable Gauge
mm
2
Wire Stripping
Length
mm
Terminal Screw
Tightening Torque
N
∙
m (in
∙
lb)
4060
R/L1, S/L2, T/L3
25
6 - 35
18
M5
•
≤ 25 mm
2
2.3 - 2.5
(19.8 - 22)
•
35 mm
2
≤
4.1 - 4.5
(36 - 40)
U/T1, V/T2, W/T3
16
4 - 25
18
M5
2.3 - 2.5
(19.8 - 22)
-, +1, +2
25
6 - 35
18
M5
•
≤ 25 mm
2
2.3 - 2.5
(19.8 - 22)
•
35 mm
2
≤
4.1 - 4.5
(36 - 40)
B1, B2
10
2.5 - 16
10
M4
1.5 - 1.7
(13.5 - 15)
10
6 - 16
-
M6
5.4 - 6.0
(47.8 - 53.1)
*1
Remove insulation from the ends of wires to expose the length of wire shown.
*2
If you turn on the internal EMC filter, the leakage current of the drive will be more than 3.5 mA. Use these closed-loop crimp
terminals or equivalent to connect a protective ground wire that has a minimum cross-sectional area of 10 mm
2
(copper wire).
•
8-4NS from JST Mfg. Co., Ltd.
•
R8-4S from NICHIFU Co.,Ltd.
■
Main Circuit Wire Gauges and Tightening Torques for UL Compliance
WARNING!
Electrical Shock Hazard. Make sure that the protective ground wire conforms to technical standards and local
safety regulations. The IEC/EN 61800-5-1:2007 standard specifies that you must wire the power supply to automatically de-
energize when the protective ground wire disconnects. If you turn on the internal EMC filter, the leakage current of the drive will
be more than 3.5 mA. You can also connect a protective ground wire that has a minimum cross-sectional area of 10 mm
2
(copper wire). If you do not obey the standards and regulations, it can cause serious injury or death.
Note:
•
The recommended wire gauges are based on drive continuous current ratings with 75 °C (167 °F) 600 V class 2 heat-resistant indoor
PVC wire. Assume these conditions:
–
Ambient temperature: 40 °C (104 °F) maximum
–
Wiring distance: 100 m (3281 ft) maximum
–
Normal duty rated current value
•
Use ter1, +2, -, B1, and B2 to connect peripheral options, for example a DC reactor or a braking resistor. Do not connect other
items to these terminals.
•
Refer to the instruction manual for each device for recommended wire gauges to connect peripheral devices or options to ter1,
+2, -, B1, and B2. Contact the manufacturer or your nearest sales representative if the recommended wire gauges for the peripheral
devices or options are out of the range of the applicable gauges for the drive.
Содержание Q2V Series
Страница 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Страница 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 143: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 143 EU Declaration of Conformity...
Страница 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Страница 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...
Страница 733: ...SIEPCYEUOQ2V01A Q2V Technical Manual 733...