544
SIEPCYEUOQ2V01A Q2V Technical Manual
12.6
F: OPTIONS
F parameters
are used to set option cards, which function as interfaces for encoders, analog I/O, digital I/O, and
fieldbus communication.
◆
F1: ENCODER
F1 parameters set the fault detection function in Speed Feedback (V/F Control). When
A1-02 = 0 [Control
Method = V/f Control]
, set
H6-01 = 3 [PI Pulse Train Function = PG Feedback]
to enable this function. For
speed feedback, connect the single-channel pulse signal from the PG encoder to pulse train input terminal PI. Use
the Slip Compensation signal to improve the accuracy of Speed Control. This function is available for Motor 1.
WARNING!
Sudden Movement Hazard. Do test runs and examine the drive to make sure that the command references are
correct. If you set the command reference incorrectly, it can cause damage to the drive or serious injury or death.
WARNING!
Sudden Movement Hazard. Make sure that the host controller circuitry has correct safety design that will let you
keep control of the motor if the drive loses speed feedback. If you do not have control of the motor, it can cause serious injury or
death.
■
F1-02: PGOpen Detection Select
No.
(Hex.)
Name
Description
Default
(Range)
F1-02
(0381)
PGOpen Detection Select
Sets the method to stop the motor or let the motor continue operating when the drive detects
PGo
[Encoder (PG) Feedback Loss]
.
1
(0 - 4)
If the drive does not detect ouput pulses from the encoder for the time set in
F1-14 [Enc PGOpen Time for
Detection]
, it will trigger
PGo
.
Note:
•
When
A1-02 = 0 [Control Method = V/f Control]
, set
H6-01 = 3 [PI Pulse Train Function = PG Feedback]
to enable this parameter.
•
Motor speed and load conditions can cause
ov [Overvoltage]
and
oC [Overcurrent]
faults.
0 : Ramp->Stop
The drive ramps the motor to stop in the deceleration time. The output terminal set for
Fault [H2-01 to H2-03 =
E]
activates.
1 : Coast->Stop
The output turns off and the motor coasts to stop. The output terminal set for
Fault [H2-01 to H2-03 = E]
activates.
2 : Fast Stop (C1-09)
The drive stops the motor in the deceleration time set in
C1-09 [Fast Stop Time]
. The output terminal set for
Fault
[H2-01 to H2-03 = E]
activates.
3 : Alarm Only
The keypad shows
PGo
and the drive continues operation. Only use this setting in special conditions to prevent
damage to the motor and machinery. The output terminal set to
Alarm [H2-01 to H2-03 = 4]
activates.
4 : No Alarm Display
The drive continues operation and does not show
PGo
on the keypad. Only use this setting in special conditions to
prevent damage to the motor and machinery.
■
F1-03: Overspeed Detection Selection
No.
(Hex.)
Name
Description
Default
(Range)
F1-03
(0382)
Overspeed Detection
Selection
Sets the method to stop the motor or let the motor continue to operate when the drive detects
oS
[Overspeed]
.
1
(0 - 3)
When the motor speed is more than the value set in
F1-08 [Overspeed Level]
for longer than the time set in
F1-09
[Overspeed Delay Time]
it will trigger
oS
.
0 : Ramp->Stop
The drive ramps the motor to stop in the deceleration time. The output terminal set for
Fault [H2-01 to H2-03 =
3]
activates.
1 : Coast->Stop
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание Q2V Series
Страница 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Страница 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 143: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 143 EU Declaration of Conformity...
Страница 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Страница 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...