2-33
H
Connecting a Regeneration Unit
M
E
1MC
X
X
1MC
1MC
12 to
24 VDC
R
T
OFF
ON
R
T
34
35
ALM
ALMCOM
ALM
ALM
U
V
W
CN2
CN1
P
N
P
N
R88A-RG08UA
Regeneration Unit
RG
JP
R
Short bar
External
regeneration
resistor
Single-phase, 200/230 VAC, 50/60 Hz (R88D-UP
jj
H(A))
Single-phase, 100/115 VAC, 50/60 Hz (R88D-UP
jj
L(A))
OMNUC U-series Servo Driver
Note 1. When using the external regeneration resistor, disconnect the short bar between the RG and
JP terminals. The internal circuit may be damaged if the external regeneration resistor is con-
nected with the shortbar still connected between the RG and JP terminals.
Note 2. Connect the external regeneration resistor between the P and RG terminals.
Note 3. The Regeneration Unit does not conform to EC Directives.
Note 4. When connecting the ALM output, form a sequence so that the power supply is shut OFF
when the contacts open. The Unit may be damaged if the ALM output is used without forming
a power shut-off sequence.
System Design and Installation
Chapter 2