46
Chapter
2
Auxiliary Output
F3SG-R
User’s Manual
System Operation and Functions
Information (Output operation mode) assigned to auxiliary output
Make sure the Position 8 of the DIP Switch is set to Configuration Tool Enabled to activate the settings by the
Configuration Tool.
Refer to
Safety Light Curtain Configuration Tool for Model F3SG (SD Manager 2) User’s Manual
for more
information on setting this function by the Configuration Tool.
Information Name
Description
(Auxiliary output is turned ON under the following condition)
Safety output information
When Safety output is in the ON state
Interlock information
Under Interlock state
Lockout information
Under error/ Lockout state
Excess power-on time
information
When power-on time exceeds power-on time threshold
Excess load switching
frequency information
When load switching frequency exceeds load switching frequency threshold
Stable-state information
When the F3SG-R is unblocked with stable light intensity
Muting information
Under Muting state
Override information
Under Override state
Muting/Override information
Under either Muting or Override state
Light level diagnosis
information
When the F3SG-R is unblocked and light intensity is within a range from 100% to 170% of ON-
threshold for 10 s or longer
Warning Zone Information
When warning zone is blocked
Blanking bream unblocked
information
When Fixed-Blanking or Floating Blanking beams are unblocked
Troubleshooting support
signal
When one of the signals of Sequence error information, Interference/vibration information and
Light level diagnosis information is in the ON state.
Designated beam output
information
When a designated beam is blocked or unblocked
Sequence error information
Under Muting sequence error state or Interlock sequence error state
Reset-input information
When Reset/EDM/Override input is in the ON state
Mute A input information
When MUTE A input is in the ON state
Mute B input information
When MUTE B input is in the ON state
EDM input information
When EDM signal input is in the ON state
Individual cascaded sensor
output (Channel 1)
When Safety output of Primary sensor in cascade connection is the ON state
Individual cascaded sensor
output (Channel 2)
When Safety output of 1st Secondary sensor in cascade connection is the ON state
Individual cascaded sensor
output (Channel 3)
When Safety output of the 2nd Secondary sensor in cascade connection is the ON state
Blanking/Warning-zone
information
When Fixed Blanking, Floating Blanking, Reduced Resolution or Warning Zone function is
enabled
Interference/vibration
information
When the F3SG-R system stops accidentally due to interference or vibration. (In case of
cascade connection, when any of cascaded segments comes under this condition.)
Pre-reset Information
Under Pre-reset state
Содержание F3SG-RA
Страница 1: ...F3SG R Series Safety Light Curtain User s Manual Cat No Z352 E1 08 http www ia omron com f3sg r...
Страница 16: ...xiv Introduction F3SG R User s Manual...
Страница 24: ...xxii Introduction F3SG R User s Manual...
Страница 44: ...20 Chapter 1 List of Models F3SG R User s Manual Overview and Specifications...
Страница 132: ...108 Chapter 2 Setting Recovery F3SG R User s Manual System Operation and Functions...
Страница 208: ...184 Chapter 4 Wiring F3SG R User s Manual Wiring Installation...
Страница 244: ...220 Chapter 6 Maintenance Checklists F3SG R User s Manual Checklists...