Chapter
2
Mu
ting
F3SG-R
User’s Manual
System Operation and Functions
3.
The muting sensor is blocked and the safety function of the F3SG-RA is disabled
Muting sensors A1 and B1 are turned OFF but A2 and B2 are ON, so the muting state is still
maintained. Safety outputs 1 and 2 are turned ON.
4.
The muting state is released
Muting sensor B2 is turned OFF, the muting state is released, and the safety function of the F3SG-RA
is enabled.
<Installation distance>
The minimum distance, D3 [m], required for muting sensors to keep the muting state enabled is :
D3 < L . . . . . Formula (3)
L [m]: Length of a workpiece
The maximum distance, d2 [m], required for muting sensors to keep the muting state enabled is :
V x T1min < d2 < V x T1max . . . . . Formula (4)
V [m/s]
: Approach speed of a workpiece
T1min [s] : Muting input time limit value (minimum). It is set as 0.1 s. (configurable)
T1max [s] : Muting input time limit value (maximum). It is set as 4 s. (configurable)
A1 F3SG-RA A2
Workpiece
Hazardous zone
B1 B2
A1
B1
F3SG-RA
B2
A2
Workpiece
Hazardous zone
Содержание F3SG-RA
Страница 1: ...F3SG R Series Safety Light Curtain User s Manual Cat No Z352 E1 08 http www ia omron com f3sg r...
Страница 16: ...xiv Introduction F3SG R User s Manual...
Страница 24: ...xxii Introduction F3SG R User s Manual...
Страница 44: ...20 Chapter 1 List of Models F3SG R User s Manual Overview and Specifications...
Страница 132: ...108 Chapter 2 Setting Recovery F3SG R User s Manual System Operation and Functions...
Страница 208: ...184 Chapter 4 Wiring F3SG R User s Manual Wiring Installation...
Страница 244: ...220 Chapter 6 Maintenance Checklists F3SG R User s Manual Checklists...