Description
Error code
Cause and measures
Cap error
4F
A cap may be detached. Attach the cap properly.
Other sensor error
38
Other sensor being cascaded caused an error. Check the indicator of the
sensor.
Blanking monitoring error
EC
An error is detected by the fixed blanking monitoring function or the floating
blanking monitoring function.
See Chapter 2 "Fixed Blanking" or "Floating Blanking" to solve th e problem.
Cascading configuration error
39, 3A, 3B
The cascading cable may be short-circuited, broken, or disconnected. Check
that the cascading cable should be tightly connected. If the cascading cable is
broken, replace it.
The number of connected sensors or beams may have exceeded the
maximum value due to cascading.
Check the configuration.
External device monitoring error
52
Relay may be welded.
Replace the relay.
The relay and the Reset line may not be properly wired.
Check the wiring with the relay.
The relay response time may be exceeding the allowable delay time.
Change the allowable delay time or replace the relay with one that has an
appropriate response time.
2-10. External Device Monitoring (EDM)
Safety output error
60, 6B, 6C
Safety output lines may be short-circuited to each other or another signal line
may be short-circuited to the safety output line.
Wire the safety output lines properly.
Communication error
30, 31, 32
The communication line or other wiring may be broken or short-circuited.
Check the cables for cascading or extension cables.
If the wiring is extended with cables other than specified, the cables used for
extension may not have performance equivalent or greater than the specified
cables. Use cables with the same performance or more than the specified
cables.
DIP Switch setting error
E7, E8
A DIP Switch setting may have been changed during operation.
Check if a DIP Switch setting was changed or not.
Settings of two DIP Switches of a receiver may be unmatched.
Check if two DIP Switches of a receiver are matched.
Содержание F3SG-RA
Страница 1: ...F3SG R Series Safety Light Curtain User s Manual Cat No Z352 E1 08 http www ia omron com f3sg r...
Страница 16: ...xiv Introduction F3SG R User s Manual...
Страница 24: ...xxii Introduction F3SG R User s Manual...
Страница 44: ...20 Chapter 1 List of Models F3SG R User s Manual Overview and Specifications...
Страница 132: ...108 Chapter 2 Setting Recovery F3SG R User s Manual System Operation and Functions...
Страница 208: ...184 Chapter 4 Wiring F3SG R User s Manual Wiring Installation...
Страница 244: ...220 Chapter 6 Maintenance Checklists F3SG R User s Manual Checklists...