30
Chapter
2
Self-Test
F3SG-R
User’s Manual
System Operation and Functions
2-6. Self-Test
2-6-1. Overview
The F3SG-R performs the Self-Test when power is turned ON (within 2 seconds) to check for errors.
Also, it regularly performs the Self-Test (within a response time) while operating.
This function cannot be cancelled.
If an error is found in the Self-Test, the F3SG-R enters the Lockout state, keeps the safety output in the
OFF state, and indicates the error at the same time.
2-6-1-1. Self-Test details
The Self-Test detects such error as described below.
Emitter
• Failure of emitter unit or circuit
• CPU failure
• Memory failure
• Failure of DIP Switch*
Receiver
• Abnormal external power supply voltage
• Failure of internal power supply circuit
• Failure of receiver unit or detection circuit
• CPU failure
• Memory failure
• Failure of safety output circuit
• Disconnected or short-circuited cable
• Failure of DIP Switch*
* The Self-Test for the DIP Switch is not available for the F3SG-RE as it does not have the DIP Switch.
F3SG-RA Series
X
F3SG-RE Series
X
Subsequently performs periodic test
Power supply
ON
OFF
Self test
ON
OFF
2 s max.
Содержание F3SG-RA
Страница 1: ...F3SG R Series Safety Light Curtain User s Manual Cat No Z352 E1 08 http www ia omron com f3sg r...
Страница 16: ...xiv Introduction F3SG R User s Manual...
Страница 24: ...xxii Introduction F3SG R User s Manual...
Страница 44: ...20 Chapter 1 List of Models F3SG R User s Manual Overview and Specifications...
Страница 132: ...108 Chapter 2 Setting Recovery F3SG R User s Manual System Operation and Functions...
Страница 208: ...184 Chapter 4 Wiring F3SG R User s Manual Wiring Installation...
Страница 244: ...220 Chapter 6 Maintenance Checklists F3SG R User s Manual Checklists...