81
F3SG-R
User’s Manual
Chapter
2
Floa
ting Bla
n
king
System Operation and Functions
E
2-15. Floating Blanking
Detection capability gets larger when the floating blanking function is used. When this function is
used, the safety distance calculation must be based on the increased detection capability for this
function.
Otherwise the machine may not stop before a person reaches to the hazardous part, resulting in
serious injury.
Responsible person must ensure that the system works as you intended after configuring floating
blanking. Failure to do so may result in serious injury.
If detection capability may get larger and a human body may pass a detection zone to reach a
hazardous source, additional safety protection equipment must be installed such as a safety
fence.
The F3SG-RA must be installed, configured, and incorporated into a machine control system by
a sufficiently trained and qualified person. Unqualified person may not be able to perform these
operations properly, which may cause a person to go undetected, resulting in serious injury
2-15-1. Overview
Floating Blanking Function
This function allows a specified number of beams in the detection zone of the F3SG-RA to move freely
while keeping the safety outputs in the ON state.
Refer to
for more information on the use in conjunction with other functions.
The Floating Blanking is not available for the F3SG-RE.
Floating Blanking Zone
All beams are configured as a floating blanking zone. If the zone overlapped with that of other function
(e.g. fixed blanking, warning zone), the other function is prioritized in the overlapped zone.
Floating Beam
Setting of the number of floating beams allows setting of the number of beams that do not turn off the
safety output. Setting of the number of floating beams can be configured by specifying the number of
beams manually or by moving an interrupting object in the detection zone. For details of teach-in
setting, see
3-3-2. Setting Floating Blanking by Teach-in
Floating Blanking Monitoring Function
F3SG-RA monitors an interrupting object in a floating blanking zone. (If the object is removed or gets
smaller, human entry may not be detected by F3SG-RA, resulting in serious injury.)
F3SG-RA enters lockout when an interrupting object becomes smaller, or removed. (Factory default setting)
It is possible to configure the blanking monitoring function to be disabled when an interrupting object is
smaller or removed.
F3SG-RA Series
X
F3SG-RE Series
Содержание F3SG-RA
Страница 1: ...F3SG R Series Safety Light Curtain User s Manual Cat No Z352 E1 08 http www ia omron com f3sg r...
Страница 16: ...xiv Introduction F3SG R User s Manual...
Страница 24: ...xxii Introduction F3SG R User s Manual...
Страница 44: ...20 Chapter 1 List of Models F3SG R User s Manual Overview and Specifications...
Страница 132: ...108 Chapter 2 Setting Recovery F3SG R User s Manual System Operation and Functions...
Страница 208: ...184 Chapter 4 Wiring F3SG R User s Manual Wiring Installation...
Страница 244: ...220 Chapter 6 Maintenance Checklists F3SG R User s Manual Checklists...