Settings for respective zone have limitations.
Refer to
2-18. Setting Zone Adjacency Conditions
Refer to
for more information on the use in conjunction with other functions.
2-14-2. Factory Default Setting
The factory default setting is Fixed Blanking Disable.
2-14-3. Setting with DIP Switch
Configuring the blanking setting of the DIP switch as Fixed Blanking Enabled enables the fixed
blanking function.
The fixed blanking monitoring function is configured as lockout.
Make sure the Position 8 of the DIP Switch is set to Configuration Tool Enabled to activate the settings by the
Configuration Tool.
Refer to
Chapter 3 Setting with DIP Switch
for more information on setting this function by the DIP Switch.
2-14-4. Setting with Configuration Tool
Some settings of functions configurable with the Configuration Tool may increase risks.
Make sure the Responsible Person conduct a thorough risk assessment analysis before
managing and changing the settings. Unintended changes to the settings may cause a
person to go undetected, resulting in serious injury.
The user can make changes to the settings by the Configuration Tool.
Setting is required for each sensor segment in case of a cascade connection.
Make sure the Position 8 of the DIP Switch is set to Configuration Tool Enabled to activate the settings by the
Configuration Tool.
Setting the Fixed Blanking Monitoring function to Disable Monitoring may create an undetectable area where a person
can interrupt the F3SG-RA without being detected, and it is not compliant with IEC 61496-2. Conduct risk assessment
analysis thoroughly before enabling this setting.
Refer to
Safety Light Curtain Configuration Tool for Model F3SG (SD Manager 2) User’s Manual
for more
information on setting this function by the Configuration Tool.
Function
Factory Default Setting
Available Parameters
Fixed Blanking
zone
Bottom beam
Disable
Enable/Disable
Top beam
1
any beam in 1-beam increments
Top beam
1
any beam in 1-beam increments
Fixed Blanking Monitoring
Lockout
Lockout/Disable monitoring/Cancel blanking zone
Number of allowable upper beams
0 beam
0 to 5 beams in 1-beam icrements
Number of allowable lower beams
0 beam
0 to 5 beams (1-beam increments)
Содержание F3SG-RA
Страница 1: ...F3SG R Series Safety Light Curtain User s Manual Cat No Z352 E1 08 http www ia omron com f3sg r...
Страница 16: ...xiv Introduction F3SG R User s Manual...
Страница 24: ...xxii Introduction F3SG R User s Manual...
Страница 44: ...20 Chapter 1 List of Models F3SG R User s Manual Overview and Specifications...
Страница 132: ...108 Chapter 2 Setting Recovery F3SG R User s Manual System Operation and Functions...
Страница 208: ...184 Chapter 4 Wiring F3SG R User s Manual Wiring Installation...
Страница 244: ...220 Chapter 6 Maintenance Checklists F3SG R User s Manual Checklists...