Timing chart
Default settings
Wiring diagram
Variable
Variable name
Value
Description
T
1min
Muting input time limit value
(minimum)
0.1 s
Minimum time difference between muting inputs A and B.
If the time difference between muting inputs A and B is smaller
than this value, a muting sequence error occurs.
T
1max
Muting input time limit value
(maximum)
4 s
Maximum time difference between muting inputs A and B.
If the time difference between muting inputs A and B is larger
than this value, a muting sequence error occurs.
T
2
Muting time limit
60 s
The duration time of the Muting function. The Muting state is
cancelled if it continues for longer than this time limit.
T
3
Maximum allowable muting
signal interruption
0.1 s
Maximum duration of a signal interruption allowed in muting
inputs A and B.
Beam state
Muting input A
ON
OFF
Muting input B
Muting state
OSSD
ON
OFF
Unblocked
Blocked
ON
OFF
Enabled
Disabled
T2 max.
T3 max.
T3 max.
T1min to T1max
80 ms max.
MUTE A : Gray
MUTE B : Pink
MUTE A : Gray
MUTE B : Pink
S1
S2
S1
S2
S1, S2:
Muting sensor
F39-JG
A-D
F39-JG
A-D
S1, S2:
Muting sensor
PNP output
NPN output
Receiver
Receiver
Power supply
0 VDC : Blue
24 VDC : Brown
0 VDC : Blue
24 VDC : Brown
0 VDC
+24 VDC
Power supply
0 VDC
+24 VDC
Содержание F3SG-RA
Страница 1: ...F3SG R Series Safety Light Curtain User s Manual Cat No Z352 E1 08 http www ia omron com f3sg r...
Страница 16: ...xiv Introduction F3SG R User s Manual...
Страница 24: ...xxii Introduction F3SG R User s Manual...
Страница 44: ...20 Chapter 1 List of Models F3SG R User s Manual Overview and Specifications...
Страница 132: ...108 Chapter 2 Setting Recovery F3SG R User s Manual System Operation and Functions...
Страница 208: ...184 Chapter 4 Wiring F3SG R User s Manual Wiring Installation...
Страница 244: ...220 Chapter 6 Maintenance Checklists F3SG R User s Manual Checklists...