1-2 Specifications
1-2-1 CX-Integrator
Specifications
Item
Specification
Series
Device type
CPU Unit model
CS1H CS1H-CPU67/66/65/64/63(-V1)
CS1G/CJ1G CS1G-CPU45/44/43/42(-V1)
Note: CompoWay/F cannot be
used with a built-in serial
port on the CPU Unit.
CS1G-H CS1G-CPU45H/44H/43H/42H
CS1H-H CS1H-CPU67H/66H/65H/64H/63H
Note: A CPU Unit with unit
version 3.0 or later must be
used when using
CompoWay/F with a
built-in serial port on the
CPU Unit
CS1D-H CS1D-CPU67H/65H
Note: When using a pre-Ver. 1.1
CS1D-H CPU Unit, use it as if it
were a CS1H-H CPU Unit.
CS Series
CS1D-S CS1D-CPU67S/65S/44S/42S
CS1G/CJ1G CJ1G-CPU45/44
Note: CompoWay/F cannot be
used with a built-in serial
port on the CPU Unit.
CJ1M CJ1M-CPU23/22/21/13/12/11
CJ1G-H CJ1G-
CPU45H/44H/43H/42H
CJ Series
CJ1H-H CJ1H-CPU67H/66H/65H
Note: A CPU Unit with unit
version 3.0 or later must
be used when using
CompoWay/F with a
built-in serial port on the
CPU Unit
CP1H-XA CP1H-XA
@@@@
-
@
CP-Series
CP1H-X CP1H-X
@@@@
-
@
Note: CompoWay/F cannot be
used with a built-in USB
port on the CPU Unit. It
can be used with a serial
communications port.
NSJ
Series
NSJ
G5D (Used for the NSJ5-TQ0
@
-G5D,
NSJ5-SQ0
@
-G5D, NSJ8-TV0
@
-G5D,
NSJ10-TV0
@
-G5D, and
NSJ12-TS0
@
-G5D.)
Note: CompoWay/F can be used
on serial port C (RS-232C
port) on the Controller
Section of the NSJ
Controller.
PLCs that are
accessible as target
PLCs
Note: The target PLC
is the PLC actually
being accessed, e.g.,
to upload/download
the PLC’s network
configurations.
Note:
The CS/CJ-series PLC must have a lot number of 030201 or later (manufactured 1
February 2003 or later) to start the CX-Designer and transfer screen data to an NS-series PT
from the CX-Designer through the PLC. The following PLCs can be used:
CS1G-H, CS1H-H, CS1D-S, CJ1M, or CJ1H-H. (The CS1D-H cannot be used.)
The following communications are possible for a directly connected target PLC.
Supported network
communications
Ethernet (Access is possible only to CS/CJ-series PLCs, NS-series PTs,
and computers with FinsGateway on the Ethernet network. For
CVM1/CV-series PLCs, only display functions are supported.)
Controller Link (Access is possible only to CS/CJ/CP-series PLCs,
NS-series PTs, and computers with FinsGateway on the Controller Link
network.) For C200H-series PLCs and CVM1/CV-series PLCs, only
display functions are supported.)
Note:
When the Controller Link Network Diagnosis application is
being used, it is possible to monitor and troubleshoot PLC models in
the Controller Link network other than CS/CJ-series PLCs.
SYSMAC LINK (Monitoring is possible only to CS/CJ-series PLCs,
NS-series PTs, and computers with FinsGateway on the SYSMAC LINK
network.)
DeviceNet (CS/CJ-series DeviceNet Units, C200H DeviceNet Master
Units, or CVM1/CV-series DeviceNet Master Units)
Note:
A C200H-DRM21-V1 or CVM1-DRM21-V1
DeviceNet Master
Unit can be used through a CS/CJ-series DeviceNet Unit.
Supported serial
communications
CompoWay/F (CS/CJ-series CPU Units must be unit version 3.0 or later.)
Serial Communications Boards and Serial Communications Units must be
unit version 1.2 or later. Only slaves for which CPS files are installed on
the computer can be accessed.
NT Links (Connection is possible only for NS-series PTs with model
numbers ending in V1 or later.)
Supported
communications
Note: Accessing PLC Communications Across Network Layers
If relay network routing tables are set, a PLC on a different network layer than the network of the
PLC connected to the CX-Integrator can be set as the target PLC.
1-10
Содержание CX-INTEGRATOR - V1.1
Страница 1: ...OPERATION MANUAL CX Integrator Ver 1 1 SYSMAC CXONE AL C E Cat No W445 E1 02...
Страница 2: ...CXONE AL C E CX Integrator Ver 1 1 Operation Manual Revised November 2005...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 13: ...xiv...
Страница 120: ...Communications Section 3 Routing Tables This section describes how to set the routing tables 3...
Страница 200: ...Communications Section 5 Ethernet This section describes the operations specific to Ethernet 5...
Страница 292: ...Communications Section 8 NT Links This section explains the settings and operations specific to the NT Link system 8...
Страница 328: ...Appendices A...
Страница 336: ......