3-2 Setting the Routing Tables
3-2-5 Transferring Routing Tables
3-2-5
Transferring Routing Tables
Use the following procedure to transfer the routing tables that were created online or
offline to PLC1. The computer must be directly connected to PLC1 and online.
1. Verify that PLC1 is connected directly to the CX-Integrator and online, display the
PLC Routing Table Window, and select
Options – Transfer to PLC
.
2. The following dialog box will be displayed to confirm the transfer. To proceed with
the transfer to the PLC, click the
Yes
Button.
3. The routing tables (local network table and relay network table) will be transferred
from the computer (CX-Integrator) to PLC1.
The following dialog box will be displayed after the transfer is completed.
Note
When transferring the FINS local routing tables, the tables can be transferred only to
the directly connected PLC (with node address 0). The tables cannot be transferred to
any other PLC in the network (i.e., to a node address other than node 0).
This step completes the transfer of the routing tables to PLC1. Use the procedure
outlined above to transfer the routing tables to PLC2 and PLC3.
Note: The following message will be displayed if a CS/CJ-series Unit with no version
number is being used and the gateway counter was set to
Expand
in the Gateway
Counter Setting Dialog Box.
Click the
Yes
Button to change the gateway counter setting to
Standard
and transfer the
routing tables.
Click the
No
Button to cancel the routing table transfer.
4. After the routing tables have been transferred, update the Online Connection
Information Window by either selecting
Update of Online Information Window
from the View Menu in the Online Connection Information Window or pressing the
F5
Key.
!
Caution
When changing or removing a routing table (see note), be sure to update
the display for the Online Connection Information Window. The display
for the Online Connection Information Window could possibly be different
from the actual network status. If operations are executed without first
updating the display, particularly online operations in the Network
Configuration Window, it could cause data to be mistakenly read or
written for the wrong network or node address or unit number.
Note:
Changing or removing a routing table refers to using the
CX-Integrator (or a CX-Integrator for another personal computer) to start
the Routing Table Component and then changing or removing a routing
table for the target PLC (either a local network table or a relay network
table).
3-21
Содержание CX-INTEGRATOR - V1.1
Страница 1: ...OPERATION MANUAL CX Integrator Ver 1 1 SYSMAC CXONE AL C E Cat No W445 E1 02...
Страница 2: ...CXONE AL C E CX Integrator Ver 1 1 Operation Manual Revised November 2005...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 13: ...xiv...
Страница 120: ...Communications Section 3 Routing Tables This section describes how to set the routing tables 3...
Страница 200: ...Communications Section 5 Ethernet This section describes the operations specific to Ethernet 5...
Страница 292: ...Communications Section 8 NT Links This section explains the settings and operations specific to the NT Link system 8...
Страница 328: ...Appendices A...
Страница 336: ......