4-3
Manually Setting Data Links
4-3-4 Creating
Data
Link Tables Offline
8 Set node address 02 as shown in the following table.
Item Data
set Description
Node address
2
−
PLC type
CS1G-
CPU45
−
Memory area
CIO
Start address
1200
Sets CIO 1200 as the data link start
address for the Area 1 local node.
Area 1
Send size
30
Sets 30 words as the send size (unit:
words) for the Area 1 local node.
Memory area
D
Start address
600
Sets D00600 as the data link start
address for the Area 2 local node.
Area 2
Send size
30
Sets 30 words as the send size (unit:
words) for the Area 2 local node.
Ordered destination nodes
1, 2, 3
Specifies the node refresh sequence.
Beginning with the start addresses,
nodes 01, 02, and 03 are set in order.
(Reception from node 01 is first,
followed by transmission from the local
node, and finally reception from node
03.)
Memory area
CIO
Data link status
start address
Start address
1300
Sets CIO 1300 as the data link status
start address.
9 Set node address 03 as shown in the following table, and then click the
Next
Button or press the
Enter
key.
Item Data
set Description
Node address
3
−
PLC type
CS1G-
CPU45
−
Memory area
IR
Start address
300
Sets IR 300 as the data link start
address for the Area 1 local node.
Area 1
Send size
40
Sets 40 words as the send size (unit:
words) for the Area 1 local node.
Memory area
DM
Start address
700
Sets DM 700 as the data link start
address for the Area 2 local node.
Area 2
Send size
40
Sets 40 words as the send size (unit:
words) for the Area 2 local node.
Ordered destination nodes
2, 1, 3
Specifies the node refresh sequence.
Beginning with the start addresses,
nodes 02, 01, and 03 are set in order.
(Reception from node 02 is first,
followed by reception from node 01, and
finally transmission from the local node
address.)
Memory area
LR
Data link status
start address
Start address
0
Sets LR0 as the data link status start
address.
4-15
Содержание CX-INTEGRATOR - V1.1
Страница 1: ...OPERATION MANUAL CX Integrator Ver 1 1 SYSMAC CXONE AL C E Cat No W445 E1 02...
Страница 2: ...CXONE AL C E CX Integrator Ver 1 1 Operation Manual Revised November 2005...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 13: ...xiv...
Страница 120: ...Communications Section 3 Routing Tables This section describes how to set the routing tables 3...
Страница 200: ...Communications Section 5 Ethernet This section describes the operations specific to Ethernet 5...
Страница 292: ...Communications Section 8 NT Links This section explains the settings and operations specific to the NT Link system 8...
Страница 328: ...Appendices A...
Страница 336: ......