4-3 Manually
Setting Data Links
4-3-5 Procedure
Using Setup Example
Setting Node Address 02
Node address 02 is set in the same way as node address 01.
Local node send area
Receive area from remote nodes
Setting Node Address 03 (Setting an Offset)
For node address 03, the procedure for setting the node refresh sequence and the
offset is as follows:
1 Select node address 03 from the node address list on the left.
2 With node address 03, the node refresh sequence does not match the default, so
the order of addresses must be changed. Change the node refresh sequence by
either clicking F4: Move Up Area or F5: Move Down Area in the Function Bar, or
pressing the F4 or F5 function keys.
F5: Move Down Area
3 Double-click on the Offset cell, and input the data size to be offset. In this example,
set the offset size to 10 words.
With this setting, 20 words sent from node 01 will be received, starting from CIO
1000, and with an offset of 10 words (i.e., CIO 1010 to CIO 1030).
4-24
Содержание CX-INTEGRATOR - V1.1
Страница 1: ...OPERATION MANUAL CX Integrator Ver 1 1 SYSMAC CXONE AL C E Cat No W445 E1 02...
Страница 2: ...CXONE AL C E CX Integrator Ver 1 1 Operation Manual Revised November 2005...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 13: ...xiv...
Страница 120: ...Communications Section 3 Routing Tables This section describes how to set the routing tables 3...
Страница 200: ...Communications Section 5 Ethernet This section describes the operations specific to Ethernet 5...
Страница 292: ...Communications Section 8 NT Links This section explains the settings and operations specific to the NT Link system 8...
Страница 328: ...Appendices A...
Страница 336: ......