Troubleshooting using the LED indicators
Section 5-1
5-1-3
Configuration Errors
If the Option Board is correctly configured, the RUN indicator will be ON and
the ERR indicator OFF. The table below shows the indicator and display pat-
terns caused by configuration errors.
Table 80 Configuration Errors
MX2
Display &
Indicators
RX
Display &
Indicators
Possible Cause(s)
Corrective Action
One of the configuration parameters
P160 - P179 has been rejected by the
Inverter.
Check (and correct) the following items:
• Is one of the parameters P160 - P179
specifying a Modbus register that does
not exist?
• If one of the parameters P160 - P169 is
specifying a double-word Modbus regis-
ter: Are both the high- and low-words
specified in sequence by two consecu-
tive parameters?
• If one of the parameters P170 - P179 is
specifying a double-word Modbus regis-
ter: Are both the high- and low-words
specified in sequence by two consecu-
tive parameters?
• Is a Modbus register specified twice in
the output parameter registers P160 -
P169?
• Is one of the output parameters P160 -
P169 specifying a Modbus register that
is read only? (A register is read-only if it
has an 'R' in the 'R/W' column).
See section B-4-2 of the MX2
Inverter user's manual.
See section 4-4 Register Num-
ber List RX Inverter user's
manual.
• Is one of the output parameters P160 -
P169 specifying a Modbus register of
which the parameter is not run-mode
editable?
Refer to section 3-2-3 of the
MX2 Inverter user's manual.
Refer to Appendix 1 of the RX-
Inverter user's manual.
Your Inverter version has not been prop-
erly verified with this version of the
Option Board (The PROFIBUS node
address in the Inverter is invalid or
absent).
Reset the Inverter to factory defaults. If the
problem persists, contact your local OMRON
representative for assistance.
Your Inverter version has not been prop-
erly verified with this version of the
Option Board (Some Option Board
parameters in the Inverter are invalid or
absent).
Reset the Inverter to factory defaults. If the
problem persists, contact your local OMRON
representative for assistance.
I111E-EN-02+3G3AX-MX2-RX-PRT+OperManual.book Seite 59 Donnerstag, 8. September 2011 11:53 11
Содержание 3G3AX-MX2-PRT-E
Страница 1: ...MX2 RX PROFIBUS Option Board Model 3G3AX MX2 PRT E 3G3AX RX PRT E USER S Manual Cat No I111E EN 02...
Страница 6: ...vi...
Страница 14: ...xiv Compliance with EC Directives...
Страница 20: ...6 Introduction to PROFIBUS Section 1 3...
Страница 36: ...22 How to mount the Option Board on the Inverter Section 2 3...
Страница 42: ...28 Configuring the Network Section 3 2...
Страница 70: ...56 Limitations Caused by Inverter Mode and Rating Selection Section 4 7...
Страница 108: ...94 APPENDIX G...
Страница 110: ...96 APPENDIX H...
Страница 113: ...97...
Страница 115: ......